5
Wiring the device
Important notes
Design of the cables
The cables used must comply with the approvals required for the location (e.g. UL).
ƒ
It is imperative to comply with the regulations concerning minimum cross-sections
ƒ
of PE conductors. The cross-section of the PE conductor must be at least as large as
the cross-section of the power connections.
The effectiveness of a shielded cable is reached by:
ƒ
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or
nickel-plated copper braid.
– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
Motor
ƒ
Motor holding brake (connected to optional motor brake control)
ƒ
Motor temperature monitoring
ƒ
Analog signals (inputs and outputs)
ƒ
System bus CAN
ƒ
Resolver
ƒ
Encoder
ƒ
The following connections need not be shielded:
Mains
ƒ
24 V supply
ƒ
Digital signals (inputs and outputs)
ƒ
Tip!
Parameter setting and configuration can be carried out using the
L-force »Engineer«. For this purpose the Online Help and the Software Manual
for the standard device will guide you.
86
EDK94SH366 DE/EN/FR/ES/IT 3.1