Technical description of the burner
4.1
Technical data
Model
Output
(1)
Delivery
(1)
Fuel
- Net calorific value
- Density
- Viscosity at 20 °C
Operation
Pump
- delivery (at 12 bar)
- pressure range
- fuel temperature
Nozzles
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
(2)
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated
output. The sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category
3" measuring accuracy, as set out in EN ISO 3746.
4.2
Electrical data
Motor IE2
Model
Electrical supply
Electric motor
Capacitor
Ignition trasformer
Electrical power consumption
Electrical protection
4.3
Models available
Designation
RL 42 BLU
Technical description of the burner
nd
2
stage
(high pressure)
st
1
stage
(low pressure)
Sound pressure
Sound power
Voltage
230-400/3/50
kW
Mcal/h
kg/h
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
3
kg/dm
2
mm
/s max
- Intermittent (min. 1 stop in 24 hours)
- Two-stage (high and low flame) and single-phase (all - nothing)
kg/h
bar
°C max
number
°C
°C max
dB(A)
rpm
W
V
A
µF/V
V1 - V2
I1 - I2
W max
Code
20027567
7
GB
RL 42 BLU
323 - 598
278 - 514
27 - 50.3
191 - 311
164 - 267
16 - 26.2
Light oil
11.8
10.2 (10.200 kcal/kg)
0.82 - 0.85
6 (1.5 °E - 6 cSt)
60
4 - 25
60
1
Boilers: water, steam, diathermic oil
0 - 40
60
76
87
RL 42 BLU
230-400V/3/50Hz
2880
1100
230/400
4.3 - 2.5
12.5/450
230 V - 2 x 12 kV
0.2 A - 30 mA
1650
IP 44
Tab. A
Tab. B
20023224