Installer setup
Follow the procedure below to personalize and
configure the thermostat according to the heating/
cooling system.
1
Press
and
seconds) until the display appears as
shown on the right.
2
Press
or
3
Press
and
to the next function.
4
When the last function is displayed, press
and
to save any changes and exit the
menu.
NOTE: If you do not press any button for 60 seconds
while you are in the setup menu, the thermostat automatically saves any changes made and exits
the menu. For programmable models only, at any time you can save the changes and exit by
pressing the Run button.
Function
1
Temperature display format
2
Time display format
3
Heating cycles per hour
4
Cooling cycles per hour
5
Compressor protection
6
Adaptive Intelligent Recovery
4
7
Application
1
Depending on your thermostat model or your system type, some functions are non-available or
non-applicable.
2
Damage can occur if the compressor is restarted too soon after shutdown. This feature forces the
compressor to wait 5 minutes before restarting. During the wait time, the message Cool On or Heat On
flashes on the screen. When the safe wait time has elapsed, the message stops flashing and the compressor
turns on.
3
Adaptive Intelligent Recovery™ allows the thermostat to "learn" how long your furnace or air conditioner
takes to reach the set temperature. Simply program the desired times and desired temperatures into the
schedule. The thermostat will determine when to activate heating or cooling so that the desired temperature
is attained at the desired time.
4
In Indoor mode, the minimum setpoint is 40°F (5°C) for frost protection. In Garage mode, the minimum
setpoint is 35°F (1.5°C) for energy savings.
simultaneously (for three
to change the option.
for one second to advance
Default
1
setting
0
0
5
3
2
1
3
1
0
0: Fahrenheit
1: Celsius
0: 12-hour display
1: 24-hour display
2 to 6 cycles per hour
• 2: 30 min (steam, gravity)
• 3: 20 min (hot water, 90%+ high-efficiency furnace)
• 4: 15 min (gas or oil)
• 5: 12 min (gas or oil)
• 6: 10 min (electric)
2 to 6 cycles per hour
0: Off
1: On
0: Off
1: On
0: Indoor mode: 40°F to 90°F (4.5°C to 32°C)
1: Garage mode: 35°F to 90°F (1.5°C to 32°C)
5
PRO 1000 / 2000 Series
Function
number
Option
number
Options