Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Wiring

WARNING
• Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Be sure to install a ground fault circuit interrupter. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that a ground fault circuit interrupter capable of handling harmonics must be used
in order to prevent any malfunction of the ground fault circuit interrupter itself.)
• Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
• Do not turn on the circuit breaker until all work is completed.
<Method of Mounting Conduit>
• When connecting indoor units for 3 rooms or more, open knockout holes without deforming the conduit mounting plate.
1) Dismount the service lid by removing the 2 screws.
2) Slide the protection plate up and remove it.
3) Pass wires through the conduit and secure them with a lock nut.
Conduit
Lock nut
English
Knockout hole
Conduit
mounting plate
Protection plate
Conduit mounting plate
Service lid
Stop valve cover
12
Tabla de contenido
loading

Este manual también es adecuado para:

3mxs24nmvju4mxs36nmvju

Tabla de contenido