Preparation For Installing The Unit; Environment - Ingeteam INGECON SUN 3Play TL Manual De Instalacion Y Uso

Ocultar thumbs Ver también para INGECON SUN 3Play TL:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 111

Preparation for installing the unit

5. Preparation for installing the unit
When deciding the location of the unit and planning your installation, you must follow a set of guidelines based on
the specifications of the unit. These guidelines are summarized in this chapter.

5.1. Environment

These units can be installed indoors and outdoors.
Situate the units in a place that is accessible for installation and maintenance work and which allows
access to the control panel.
Avoid corrosive environments that may affect the proper operation of the inverter.
Do not leave objects on top of the unit or its sides, as they may block the ventilation and cause high
temperatures.
Do not expose the inverters to direct sunlight.
Do not install the units in inhabited rooms, due to the noise produced during operation.
If they are installed inside a closed space (room, hut, etc.), provide adequate ventilation. The operating
range of the units depends on the environmental temperature, therefore a lack of ventilation may limit
their capacity.
If more than one inverter is installed, make sure the hot air extraction of one does not interfere with the
correct ventilation of another, leaving a lateral separation of at least 2 meters.
Environmental air temperature
Hot air
ABS2011IQM01_D - Installation and Operation Manual
Ingeteam
DE
EN
ES
FR
IT
PT
73
Tabla de contenido

Solución de problemas

loading

Tabla de contenido