Ingeteam
Preparation for installing the unit
INFO
For more information request document ABS0000IMC04 from Ingeteam.
•
Keep the following minimum distances free of obstacles.
3 0 c m
6 0 c m
6 0 c m
3 0 c m *
* as long as there is enough space for installing the required cables.
5.2. Environmental conditions
Environmental operating conditions indicated in section "2.9. Specification table" must be taken into account
when choosing the location of the unit.
It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature
variations. For this reason, apart from the unit's own protection, it is necessary to monitor these units once they
have been started up on sites where the conditions described above are not expected to be present.
In the event of condensation, never apply voltage to the unit.
5.3. Supporting Surface and Fastening
These inverters must be installed in accordance with the specifications in the following figure. The permitted
positive inclination is within the range of 0 to 90º. The installation with negative inclination (example on the right)
is not permitted.
74
ABS2011IQM01_D - Installation and Operation Manual