Technical Specifications; Functional Characteristics - Comunello Automation CU Instrucciones De Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 35
PRESCRIPTIONS
The control unit is not equipped with a device for disconnection of the
230 Vac power supply line. It is therefore the responsibility of the installer
to fit a disconnection device in the electrical system. The disconnection
device must be of the category III overvoltage all-pole circuit breaker.
This device must be positioned in such a way as to protect it against
inadvertent reconnection in compliance with the requirements of EN
12453 point 5.2.9. Wiring of the external electrical devices to the
control unit must be carried out in compliance with the prescriptions
of EN 60204-1 as amended by EN 12453 point 5.2.7. The maximum
diameter of power feeding cables is 14 mm; fixing of power feeding and
connection cables must be assured by fitting cable glands, which can
be supplied as optionals.
• The power input cables must be of the standardized flexible type with
polychloroprene sheath (H05RN-F) having minimum conductor size of 1
mm
.
2
• During the installation operations, take care to use cable with double
insulation only (sheathed cables) for both of mains voltage connections
(230V) and extra-low voltage connections (SELV). Use exclusively
plastic cable trays, separated for mains voltage wiring (230V) and extra-
low voltage wiring (SELV).
• The extra low voltage conductors must be physically separated (at
least 4 mm in air) from the mains voltage wires, or shall be adequately
insulated with extra insulation with a thickness of at least 1 mm.
• Upstream of main supply, install a device that ensures the complete
omnipolar disconnection (cut-off switch) of the power supply, with a
contact opening gap of at least 3mm in each pole. These disconnecting
devices shall be places in the power supply wiring in compliance with
the installation standards and must be directly connected to the supply
terminals.
• When drilling the outer case to insert the power and connection cables
and when fitting the cable glands, take care to install all the parts in
a manner that maintains the IP protection characteristics of the box
unchanged as far as possible. Ensure the cables are fixed in a stable
and secure manner.
• The rear of the box is equipped with knockouts for wall fixing (knockouts
for fixing holes using anchor bolts or holes for fixing with screws). Take
all the measures required to ensure the installation procedures do not
affect the IP rating.
• If required, a pushbutton panel for manual control of the gate must be
installed in a position such as to ensure the user is not placed in danger.
• The operator utilized to move the gate must be in compliance with the
prescriptions of EN 12453, point 5.2.7.
• Foto+ output must be used for photocells. Alternative uses of this output
are not permitted.
• At each operating cycle, the control unit can test the photocells
operation to ensure protection against failure of anti-crushing protective
devices according to Category 2 in compliance with the prescriptions
of EN 12453 point 5.1.1.6. It follows that if the safety devices are not
connected or are faulty, operation of the control unit will be inhibited.
• The device can be used by children no older than 8 years old and
people with reduced physical, sensory or mental capabilities, or lack
of experience or without the required knowledge, but only under
surveillance or after having received instructions about the safe use of
the device and the hazards inherent in it. Children should not play with
the device. Cleaning and maintenance should not be carried out by
children without supervision.
For correct operation of the radio receiver section, when using two or more
control units it is good practice to install them at a minimum distance of 3
metres from one another.
All operations that require the control unit box to be opened (connection of
cables, programming, etc.) must be carried out by expert personnel at the
time of installation.
IMPORTANT INFORMATION FOR USERS
• The device must not be used by minors or psychologically-physically
differently-abled persons unless they are supervised or duly instructed
on the operation and methods of use.
• Do not let children play with the device and keep the remotes out of their
reach.
• IMPORTANT: keep this instruction manual and comply with the safety
prescriptions set down herein. Failure to comply with the prescriptions
may cause damage and serious accidents.
18
COMUNELLO ®Copyright 2014 - All right reserved
Frequently examine the system to identify any signs of damage. Do not use
the device if the enclosure is in need of repair (re-programming, repair or
modification of the installation); contact technical service.

TECHNICAL SPECIFICATIONS

Power supply:
Flashing light output:
Operator outputs:
Electric lock output:
Photocells power supply:
LV safeties and controls:
Working temperature:
Radio receiver:
Transmitters:
Max TX codes stored in memory: 120 (CODE o CODE PED)
Board dimensions:
PRELIMINARY CHECKS
• Check that the product in the pack is intact and in good condition.
• Check that the place of installation is suitable and in compliance with the
minimum dimensions shown in FIG. 1.
INSTALLATION
• Drill the box in the four corners and then fix the photocells to the wall
(FIG. 2).
• Drill a hole in the underside of the box for the cable inlet. (FIG. 3). The
use of cable glands is recommended.
CONNECTIONS
CN1:
L:
230 V~ line input (phase).
N:
230 V~ line input (neutral).
OPEN1:
Operator 1 opening output.
COM1:
Operator 1 output common.
CLOSE1:
Operator 1 closing output.
OPEN2:
Operator 2 opening output.
COM2:
Operator 2 output common.
CLOSE2:
Operator 2 closing output.
CN2:
ELS:
Voltage-free contact Electric Lock output.
ELS:
Voltage-free contact Electric Lock output.
LAMP+:
Flashing light output (24 V~ 4W max).
FOTO+:
Photocells Control and Power Supply (24V~ 5W max).
GND:
Common power supply (GND).
SAFE2:
Safety Device 2 Input (NC).
SAFE1:
Safety Device 1 Input (NC).
GND:
Common GND input.
PED:
Pedestrian Pushbutton Input (NO).
PP:
Open/Close command Pushbutton input (NO).
ANT:
Antenna Ground Input.
ANT+:
Antenna Hot pole input.
TRANSFORMER CONNECTIONS
CN3 1st:
1: 230 V~ Transformer Primary Winding Input.
2: 230 V~ Transformer Primary Winding Input.
CN4 2nd:
1: Transformer SEC 1 Output 12.5V 0.17A no-load voltages.
2: Transformer SEC 1 Output 12.5V 0.17A no-load voltages.
3: Transformer SEC 2 Output 24.5V 0.4A no-load voltages.
4: Transformer SEC 2 Output 24.5V 0.4A no-load voltages.

FUNCTIONAL CHARACTERISTICS

AUTOMATIC OPERATION:
When either the remote or the low voltage pushbutton panel is used to
control the gate, operation is as follows:
the first command opens the gate until motor time elapses or until the
gate reaches its opening limit position; the second command closes the
gate; if another command is transmitted before motor time has elapsed
or before one of the two limit stops has been reached, the control unit
reverses the movement direction during both opening and closing.
230 V~ 50Hz 1600W max.
24 V~ 4W max.
230 V~ 2 x 500 W max.
Voltage-free contact (24V 5A max.)
24 V~ 5 W max.
24 Vcc
-20 ÷ 55 °C
433 Mhz
18 Bit o Rolling Code
100x105 mm
Tabla de contenido
loading

Tabla de contenido