LED Error Code Display
System Alert
Silenced audible alarm
Pump status
AC power
*
NOTE: If your AC power is off and the unit is dead (no LEDs lighted, no audible alarm, pump isn't running),
check for reversed battery connections to the charger/controller.
**
Charger was charging at a very low level to try to bring a dead battery back to life, but the battery took too long
to charge. Try resetting the charger once or twice (push the 'System Test' and 'Silence Alarm' buttons at the same
time to reset the charger).
***
Thermal Runaway condition
=
LED is ON Continuously
TABLE IV – Error Code Displays (LEDs Flashing)
Control Button:
Result of Pushing Button:
System Test
Pump starts and all LEDs light up.
Will reset the 'Pump Status' LED.
When pushed with the 'Silence Alarm' button, the Charger/Controller microprocessor resets and error code resets.
Silence Alarm
Toggle; Prevents the audible alarm sounding. Press and release to reset.
Flood Light
Toggles the flood light on the Charger/Controller on and off.
TABLE V – Control Button Functions
Charging
Battery status
Condition
= Excessive battery drain;
= Battery will not take a charge***;
= Reversed battery connections;
= Wrong battery voltage;
= Failed pre-qualification test – 1**;
= Failed pre-qualification test – 2**;
= Charge time monitor – 1;
= Charge time monitor – 2;
= Battery Charge is Below 20%;
=
LED is Flashing (Fast)
Error Condition and Corrective Action
NOTE: When the 'System Alert' LED is flashing,
look for one of the following error conditions.
Stop pump, allow battery to charge (AC must be on)
Replace battery with a new 12V lead-acid battery
Connect + to + and – to –.*
Replace battery with a new 12V lead-acid battery
Replace battery with a new 12V lead-acid battery
Replace battery with a new 12V lead-acid battery
Check battery for damage to cells; replace battery
Check battery for damage to cells; replace battery
Pump will shut down, battery is not charging. Replace
battery.
=
LED is Flashing (Slow)
Action
=
LED is OFF