IL17569BS
Fecha Efectiva: 06/03
Página 4-16
Pantalla "Alarms" (Alarmas):
50P-3 PH IOC Alarm
Pickup:
Disable
Delay (c):
Direction:
Both
50R-3 IR IOC Alarm
Pickup:
Disable
Delay (c):
Direction:
Both
47-2 V Unbal Alarm
Threshold V:
50
% (V2/V1):
40
Delay (c):
60
27M-2 Under V Alarm
Phase:
Any One
Threshold V:
Disable
Delay (c):
27A-2 Under V Alarm
Threshold:
Disable
Delay (c):
59N-2 OV Alarm
Threshold:
Disable
Delay (c):
1200
81U-2 Under Freq Al
Threshold:
Disable
Delay (c):
32-3 Power Alarm
Threshold:
Disable
Delay (c):
Página 4-16
0
0
50P-3 PH IOC Alarm
50X-3 IX IOC Alarm
50R-3 IR IOC Alarm
46-2 I Unbal Alarm
47-2 V Unbal Alarm
59M-2 Over V Alarm
27M-2 Under V Alarm
0
59A-2 Over V Alarm
27A-2 Under V Alarm
59N-2 OV Definition
0
81O-2 Over Freq Alm
81U-2 Under Freq Al
32-3 Pwr Definition
32-3 Power Alarm
0
Diccionario
Both
0
Delay
Disable
IOC
Over
Phase
Pickup
Reset
Threshold
Unbal
Under
Para más información visite:
FP-5000
Alarms
59N-2 OV Alarm
Ambos
Retardo
Deshabilitado
Sobreintensidad Instantánea
Sobre
Fase
Levante
Reponer
Umbral
Desbalance
Bajo
www.cutler-hammer.eaton.com
50X-3 IX IOC Alarm
Pickup:
Disable
Delay (c):
0
Direction:
Both
46-2 I Unbal Alarm
Threshold:
0.10
% Unbal (I2/I1):
40
Delay (c):
60
59M-2 Over V Alarm
Phase:
Any One
Threshold V:
Disable
Delay (c):
0
59A-2 Over V Alarm
Threshold:
Disable
Delay (c):
0
59N-2 OV Definition
Source:
Calc
Criterion:
Phasor
81O-2 Over Freq Alm
Threshold:
Disable
Delay (c):
0
32-3 Pwr Definition
Direction:
Reverse
Criterion:
Over
Fecha Efectiva: 06/03