INSTALLATION
Connection of safety transmitter-receiver photocells in closing (SG.C)
FT06
Safety contact connection in opening (SG.A) for pedestrian door
A
B
44
Installation Manual
COM
SG.C
– FT (test)
+ FT (test)
P155I
P155P
We
recommend
installing
photocells.
1 Complete the connections as shown in the figure.
If neither photocells nor a mechanical strip are used,
place an electrical bridge between cable connectors
3 and 4 of the control board (COM - SG.C).
2 Duly programme the operator:
Closing photocells with pre-testing: C511
Closing photocells without pre-testing: C510
Without closing photocells: C500
For further details on programming, see "Starting
up and programming" on page 46.
If there is a pedestrian door (B) in the main
door (A), make sure the main door does not
open when the pedestrian door is open by
installing an NC contact (normally closed).
1 Install the NC contact in the door so the contact
remains closed when the pedestrian door (B) is
closed, and opens when the pedestrian door (B)
opens.
2 Complete the connections as shown in the figure
(cable connectors 3 and 5).
3 Programme the operator:
Contact installed: C410.
Programme C400 if the contact is not installed
because there is no pedestrian door in the main
door.
For further details on programming, see "Starting
up and programming" on page 46.