16
MicroLogix™ 1200 Programmable Controllers
Wire Requirements
Wire Type
Solid
Cu-90°C (194°F)
Stranded
Cu-90°C (194°F)
Wiring torque = 0.791 Nm (7 in-lb) rated
ATTENTION
Wiring Recommendation
When wiring without spade lugs, keep the finger-safe covers in place. Loosen the
terminal screw and route the wires through the opening in the finger-safe cover.
Tighten the terminal screw, making sure the pressure plate secures the wire.
Publication 1762-IN006D-MU-P - March 2004
Wire Size (2 wire maximum per terminal screw)
#14 to #22 AWG
#16 to #22 AWG
Be careful when stripping wires. Wire fragments that fall into
the controller could cause damage. Once wiring is complete,
be sure the controller is free of all metal fragments before
removing the protective debris strip. Failure to remove the
strip before operating can cause overheating.
Finger-safe cover