P
ACCURACY
Exactidão na energia activa :
Exactidão na energia reactiva :
MARCAÇÃO CE
The DIRIS A20 complies with :
• The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May 1989,
modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
• Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July 1993.
COMPATIBILIDADE ELECTROMAGNÉTICA
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency fields:
Immunity to electrical fast transients/bursts:
Immunity to impulse waves:
Immunity to conducted disturbances:
Immunity to power frequency magnetic fields:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
CLIMA
Operating-temperature range:
Storage temperature range:
Humidity:
Saling fog:
CARACTERÍSTICAS MECÂNICAS
Vibration from 10 to 50 Hz :
ISOLAÇÃO
Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
Electric security:
UL - CSA Approval
Auxiliary supply (UL-CSA Approval)
Standard
Certificate
Indoor use
Altitude up to 2000 m or above 2000 m if specified by the manufacturer (see clause D.9 for further information)
Temperature 0 to 40°C. Maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative
humidity at 40°C
Transient overvoltages according to installations categories.
Overvoltage categories I,II and III.
For mains supply the minimum and normam category is II.
SOCOMEC - Réf. : 876 580 C
IEC 62053-23 classe 0,5S
IEC 62053-23 classe 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level III
IEC 61000-4-5 - Level III
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level III
CISPR11 - Class A
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
III (480 VAC ph /ph)
2
IEC 60947-1 - V imp: 4 kV
Class II
IEC 61010-1
110 to 240 V AC
120 to 250 V DC
UL 61010-1
CSA-C22.2 No. 61010-1
UL file No: E257746
CSA report No. for DIRIS A20: 1810571
CSA report No. for DIRIS A40: 1810577
DIRIS A20
CARACTERÍSTICAS TÉCNICAS
49