Sinus Filter - KEB COMBIVERT F4-S Serie Manual De Instrucciones

Circuito de potencia
Ocultar thumbs Ver también para COMBIVERT F4-S Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 79

3.3.2 Sinus filter

230V-Class, up to f
Number
For
COMBIVERT
1
07
2
09
3
10
4
12
5
13
6
14
8
15
9
16
Via the pulse duration modulation output voltage of the frequency inverters
a voltage rise of du/dt of 5...10 kV/µs can occur dependent on the used
power modules, control process, motor line length and type of the motor.
Installation of KEB sinus filters reduce the speed of the voltage rise
between the phases of mains conditions, that no negative influences to
the long-time behaviour of the winding insulation of three-phase current
motors have to be expected. The standard-sinus filters are made for an
output frequency of max. 120 Hz.
max. 120Hz, for 4kHz switching frequency, IP00, VBG4, T 40/F
out
Part number
[A]
00.90.428-5099 4,1 125 110 180 55 100 8
00.90.428-5129 9,5 155 130 210 72 130 8
00.90.428-5139
12
00.90.428-5149 16,5 190 150 220 68 170 8
00.90.428-5159
24
00.90.428-5169
33
00.90.428-5189
50
00.90.428-5199
60
Accessories
A
d
n
1
n
2
I
Dimensions
Mounting
N
A
B
C
n1
190 140 220 58 170 8
210 165 240 82 180 8
240 195 280 106 190 11
240 220 295 126 190 11
300 355 355 121 240 11
C
B
Terminals Weight
n2
d
[mm²]
[kg]
4
4
10
10
10
16
35
35
GB - 37
GB
3,2
6,8
8
12
12
20
30
38
Tabla de contenido
loading

Este manual también es adecuado para:

Combivert f4-c serieCombivert f4-f serie

Tabla de contenido