8.9 Connecting the low-pressure pressure switch
To comply with the KIWA standard it is necessary to connect a low-pressure pressure switch on the pump intake, set
at such a pressure that it intervenes in the event of water lack.
The pressure switch must be connected to contact N of the E.Box and the contact must open if the pressure falls
below the minimum value. If the KIWA low pressure alarm trips, the set stops and it can be reset only manually, as
required by the KIWA standard.
8.10 Setting with the display, wizard
The E.box D can be configured with a simple wizard. The device asks the user for all the parameters necessary for its
configuration. If necessary, it can be loaded by pressing the "set" + "+" keys when switching on. To navigate in the
wizard, use the following keys:
"mode" to accept the parameter displayed and move on to the next,
"mode" held down for more than 1 second to return to choose the parameter,
"-" e "+" to vary the value of the parameter.