T5S_DI is the target temperature of water in the domestic
hot water tank in the DISINFECT function.
t_DI_HIGHTEMP is the time that the hot water will last.
t_DI_MAX is the time that disinfection will last. The
change of domestic water temperature is described in the
picture below:
T5
t_DI_HIGHTEMP
T5S_DI
T5S
t_DI_MAX
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in FOR
SERVICEMAN "T5S_DI" after a disinfection operation.
NOTE
If booster heater is not available(refer to 10.7
Field settings/Other heating source), please
disable DISINFECT, because the temperature of
water from heat pump is not high enough, and
the unit will stay in Disinfect mode for a long
time, which will effect space heating.
WARNING
If this high domestic hot water temperature can
be a potential risk for human injuries, a mixing
valve (field supply) should be installed at the hot
water outlet connection of the domestic hot
water tank. This mixing valve will ensure that the
hot water temperature at the hot water tap never
rises above a set maximum value. This
maximum allowable hot water temperature shall
be selected according to local laws and regula-
tions.
To set the priority between domestic water heating
and space operation Go to SERVICEMAN>DHW
MODE SETTING>1.4DHW PRIORITY:
1.4 DHW PRIORITY
t_DHWHP_MAX
t_DHWHP_RESTRICT
SCROLL
The function of the DHW PRIORITY is used to set the
operation priority between domestic water heating and
space (heating/cooling) operation. You can use
to scroll and adjust parameters.
Using BACK to exit.
t_DHWHP_MAX is the maximum continuous working
period of the heat pump in DHW PRIORITY mode.
t_DHWHP_RESTRICT is the operation time for the space
heating/cooling operation.
The suggested value of t_DHWHP_MAX is listed below:
t
If DHW PRIORITY is enabled, the operation of the unit is
described in the picture below:
Min (T5S,Tstop)-dT5_on
120MIN
30MIN
and
147
NOTE
If ROOM TEMP is enabled(refer to 10.7 Field
setting/TEMP. TYPE SETTING), it is suggested
that set t_DHWHP_RESTRICT to 10min.
Unit
volume of tank
(kW)
/L
300
12~16
250
200
200
5~7
150
100
T5
Min (T5S,Tstop)
Space
heating/
Heating
cooling
water
operation
t_DHWHP_max
If NON is selected in the DHW PRIORITY mode, when it
is available and the space heating/cooling is OFF, the
heat pump will heat the domestic water as required. If
space heating/cooling is ON, the domestic water will be
heated by booster heater(if booster heater is available).
5 If the DHW pump( P_d) is avaliable, Go to FOR
SERVICEMAN >DHW MODE SETTING>1.5DHW PUMP
and select "YES", when "OK" pressed, the following page
will appear,You can use
adjust parameters. Use BACK to exit.
1.5 DHW PUMP
TIMER RUNNING
DISINFECT
PUMP RUNNING TIME
ON/OFF
ON/OFF
SCROLL
When the TIMER RUNNING is ON, the DHW pump will
run as timed and keeps running for an certain time (as
defined in PUMP RUNNING TIME), this can ensure the
temperature of water in the system are uniform.
t_DHWHP_MAX
min
90
75
60
90
70
50
Restart
Heating
Time
water
t_DHWHP_restrict
and
to scroll and
ON
ON
10MIN