8. Boiler start-up... |
84
e. Long boiler downtime and emergency stop.
In case of long downtime:
•
press the main switch, disconnect the boiler pump,
the circulating pump and the burner
•
disconnect the power supply
•
open the door slightly to air out the exchanger
CAUTION!
FREEZE PROTECTION FUNCTION IS NOT WORKING
WITH DISCONNECTED POWER SUPPLY.
•
close all valves
•
drain the boiler and the heating system via drain valve; open all cut-off,
control and vent valves to avoid freezing
•
bottom door must be open to avoid condensation
CAUTION!
RAPID BOILER COOLING MAY INCREASE THE EXTENT OF DAMAGE.
Emergency stop may be caused by:
•
no safety valve operation at exceeded allowable pressure,
•
pressure section leakage,
•
pressure section deformation,
•
boiler room or auxiliary equipment explosion or fire,
•
drain valve leakage,
•
safety or control device failure,
•
pressure gauge failure,
•
circulating pump failure,
•
flue gas explosion,
•
pressure section fitting or welded joint leakage,
•
auxiliary equipment failure,
•
other faults that cannot be removed during boiler operation due
to safety or technical reasons.
Emergency procedure:
•
stop the boiler immediately (use the main power switch outside the
boiler room, if required)
•
use suitable fire-fighting measures (extinguishers) in case of a fire
UWAGA!!!
WPRZYPADKU PALENIA PELLETEM NALEŻY ZDEMONTOWAĆ
RUSZT ŻELIWNY WRAZ Z POPRZECZKĄ. (PATRZ PUNKT
URUCHOMIENIE KOTŁA NA PALIWIE - DREWNO)
Experts in biomass heating
9. Uruchomienie kotła na paliwie – drewno
9. Uruchomienie kotła na paliwie – drewno
Procedura zmiany paliwa pellet - drewno:
1.
Na panelu sterownika ustawić tryb OFF – poczekać aż kocioł ostygnie
2.
Wybrać rodzaj paliwa – „ruszt - drewno"
3.
Ułożyć dodatkowe ruszta w kotle
4.
Włożyć kawałki papieru na ruszta
5.
Na rusztach ułożyć kawałki suchego drewna( wymiar C oznacza
maksymalny poziom paliwa)
6.
Podpalić zapałkami kawałki papieru
7.
Zamknąć drzwiczki kotła
8.
Panel kotła ustawic w tryb ON
9.
Ustawić zadaną temperaturę kotła 70°C
UWAGA!!!
PODCZAS PALENIA DREWNEM W KOMORZE ZASYPOWE NALEŻY
PILNOWAĆ ABY TEMPERATURA SPALIN NIE PRZEKRACZAŁA 200°C.
Twin Bio Luxury User Manual – EN 03.17