Daikin VRV W T Serie Manual De Instalación página 27

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Example of refrigerant piping (8 indoor units are connected)
First outside unit
Outside unit
multi connection
piping kit
r
a
b
A
d
B1
g
e
f
D
1
2
Example for refrigerant branch using REFNET joint and REFNET header for systems and each pipe length as shown below.
Outside system: RWEQ264TATJU (RWEQ144TATJU+RWEQ120TATJU)
Total length of liquid piping: 285 ft
Total capacity of indoor unit: 104.5%
Branch Selector units
BS4Q54T×1, BSQ60T×1, BSQ96T×1
Indoor units
FXMQ type: 18×1, 24×2, 36×1, 54×1
FXFQ type: 36×2
Other: 48×1
Liquid piping
a: Ø3/4 × 60 ft
e: Ø1/4 × 15 ft
b: Ø5/8 × 20 ft
f: Ø3/8 × 10 ft
c: Ø1/2 × 10 ft
g: Ø3/8 × 10 ft
d: Ø3/8 × 15 ft
h: Ø3/8 × 15 ft
[A]= 0.7×1 + 0.2×1 + 0.4×1 = 1.3 lbs.
BS4Q54T×1
BSQ96T×1
BSQ60T×1
[C]= 0.25×1 + 0.16×2 + 0.25×1 + 0.00×1 + 0.53×2 + 0.00×1 = 1.88 lbs.
FXMQ18×1
FXMQ36×1
FXMQ24×2
[B]= Min (6.61 lbs., 1.88 lbs.) = 1.88 lbs.
R= ( 60×0.175 + 20×0.121 + 35×0.081 + 155×0.040 + 15×0.015 ) × 1.04 + 1.3 + 1.88
a
b
= 26.247 ⇒ 26.2 lbs.
Round off in units of 0.1 lbs.
INFORMATION
Piping length is considered by the distance from the
outside unit to the farthest indoor unit.
RWEQ96~432TATJU + RWEQ96~432TAYDU
VRV W T-Series water-cooled system air conditioner
4P484115-1A – 2017.10
Outside unit
B2
s
REFNET joint (A-E)
c
B
j
B2
k
i
h
3
4
5
i: Ø3/8 × 20 ft
m: Ø3/8 × 15 ft
j: Ø3/8 × 10 ft
n: Ø3/8 × 15 ft
k: Ø3/8 × 10 ft
o: Ø3/8 × 10 ft
ℓ: Ø3/8 × 15 ft
p: Ø3/8 × 10 ft
FXFQ36×2
FXMQ54×1
Other48×1
c, r, s
d, f, g, h, i, j,
e
k, ℓ, m, n, o, p
B1
: Branch Selector unit (multi)
B3
: Branch Selector unit (single)
,
C
B3
m
E
n
6
r: Ø1/2 × 10 ft
s: Ø1/2 × 15 ft
[A]
[B]
5 Installation
1
-
7
: Indoor units (cooling/heating
selectable)
8
: Indoor unit (cooling only)
(*3)
p
o
7
8
Installation manual
27
Tabla de contenido
loading

Tabla de contenido