2.1. Rear panel view

1. RS-232 communication port
4. Share current port (depends on the model)
Stage Fan
|
8. External battery terminal (dependes on the model)
10. Input/Output Terminal (refer to Diagram 2 for details)
13. Output grounding terminal
16. Bypass Input terminal (only for dual input unit)

2.2. Setup the UPS

Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following
instructions by professional personnel.
Step 1. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazard of
electric shock or fire.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS‟s
maximum input current. Otherwise the receptacle may be burned and destroyed.
Step 2. Switch off the mains switch in the building before installation.
Step 3. Turn off all the connected devices before connecting to the UPS.
Note 1: The cable for 10K/10KL should be able to withstand over 40A current. It is recommended to use AWG 10 or
thicker wire for Phase and AWG 8 or thicker wire for Neutral for safety and efficiency.
Note 2: The cable for 20K/20KL should be able to withstand over 63A current. It is recommended to use AWG 8 or thicker
wire for Phase and AWG 6 or thicker wire for Neutral for safety and efficiency.
Note 3: The selections for color of wires should be followed by the local electrical laws and regulations.
Segurança e harmonia
ININTERRUPTA
PH 9273 (10K) / PH 9293 (20K)
|
2. USB communication port
|
5. Parallel port (depends on the model)
|
14. Output terminal: connect to mission-critical loads
|

2. Installation and setup

Diagram 2: 10K/20K Input/Output Terminal
|
3. Emergency power off function connector (EPO connector)
|
9. Bypass Input Circuit Breaker (only for dual input unit)
|
11. Line Input circuit breaker
17. Input Grounding terminal
| 6. Intelligent slot
|
7. Power
|
12. Maintenance bypass switch |
|
15. Line input terminal
PH 9273 | PH 9293
Uninterruptable Power Supply
EN
|
|
65