12. Installation

EN

12.1. Unpacking and Inspection

12.1.1. Unpack the packaging and check the package contents. The shipping package contains:
1. A UPS
2. A user manual
3. A communication cable
4. A battery cable (for 6KS/10KS only)
12.1.2. Inspect the appearance of the UPS to see if there is any damage during transportation. Do not turn on the unit
and notify the carrier and dealer immediately if there is any damage or lacking of some parts.

12.2. Input and output power cords and protective earth ground installation.

12.2.1. Notes for installation
1. The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and
corrosive agents.
2. Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of space on each
side.
3. Condensation to water drops may occur if the UPS is unpacked in a very low temperature environment. In this
case it is necessary to wait until the UPS is fully dried inside out before proceeding installation and use.
Otherwise there are hazards of electric shock.
12.2.2. Installation
Installation and wiring must be performed in accordance with the local electric code and the following instructions by
professional personnel.
For safety, please cut off the mains power switch before installation. The battery breaker also needs to be cut off if it is a
long backup time model ("S" model).
1. Open the terminal block cover located on the rear panel of the UPS, please refer to the appearance diagram.
2. For 6K(S) UPS, it is recommended to select the UL1015 10AWG(6mm2) wire or other insulated wire which
complies with AWG Standard for the UPS input and output wirings.
3. For 10K(S), it is recommended to select the UL1015 8AWG(10mm2) wire or other insulated wire which
complies with AWG Standard for the UPS input and output wirings.
Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the
UPS's maximum input current. Otherwise the receptacle may be burned and destroyed.
4. Connect the input and output wires to the corresponding input and output terminals according to the following
diagram.
Note: you must make sure that the input and output wires and the input and output terminals are connected
tightly.
Input Ground
Input Neutral
74
PH 9701 | PH 9720 | PH 9735 | PH 9765 | PH 9715
Uninterruptable Power Supply
Input Line
JP1
Input and output Terminal Block wiring diagram of 6K(S)/10K(S)
Output Ground
Output Neutral
Output Line