18: Output A voltage calibration
Interface
19: Output B voltage calibration
Interface
20: Output C voltage calibration
Interface
Segurança e harmonia
ININTERRUPTA
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output A voltage, and
you can calibrate it by pressing Up or Down according to the measurement from an
external voltage meter. The calibration result will be effective by pressing Enter. The
calibration range is limited within +/-9V. This function is normally used for parallel
operation.
Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3: it shows the internal measurement value of the output B voltage, and
you can calibrate it by pressing Up or Down according to the measurement from an
external voltage meter. The calibration result will be effective by pressing Enter. The
calibration range is limited within +/-9V. This function is normally used for parallel
operation.
*It will display number 1 under OP.V to represent the output B voltage.
Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the output C voltage, and
you can calibrate it by pressing Up or Down according to the measurement from an
external voltage meter. The calibration result will be effective by pressing Enter. The
calibration range is limited within +/-9V. This function is normally used for parallel
operation.
*It will display number 2 under OP.V to represent the output C voltage.