3. Operations
EN
08: Bypass mode setting
Interface
09: Maximum battery discharge time setting
Interface
10: Reserved
Interface
11: Reserved
Interface
78
PH 9273 | PH 9293
Uninterruptable Power Supply
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass mode depending on
bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it‟s not allowed for running in Bypass mode
under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic bypass is acceptable, but manual
bypass is not allowed. Manual bypass means users manually operate UPS for Bypass
mode. For example, pressing OFF button in AC mode to turn into Bypass mode.
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0min to 999min. UPS will shut down
to protect battery if the discharge time arrives before the battery is under voltage. The
default value is 990min.
DIS: Disable battery discharge protection and backup time will depend on battery
capacity.
Setting
RESERVED FOR FUTURE OPTIONS
Setting
RESERVED FOR FUTURE OPTIONS