Apéndice 3 Diagrama Esquemático - Emerson NetSure 501 A50 Manual De Usuario

Sistema de fuente de potencia en subrack de 19-pulgadas
Tabla de contenido
Distribution Unit
Multifunction Unit
Rectifier Unit
230VAC
Note:
1. The AC distribution has 3 schemes, determined by user requirement. Refer to diagram (2).
2. The maximum output current of the MFU is 150A.
3. The number of the 1QFx and 2QFx in MFU is configurable. The total width of the load MCBs should be smaller than 190mm.
4. The DU is optional. The number of the 3QFx, 4QFx and 5QFx in MFU is configurable. The total width of the load MCBs should be smaller than 410mm.
5. The monitoring module can be M501D or M800D.
6. The number of the battery MCBs can be 2 or 3.
7. The LLVD contactor KM2 is configurable.
Apéndice 3 Diagrama Esquemático
Signal Board
2Q Fx
Monitor Back Board
230VAC
230VAC
230VAC
Figura 4 Diagrama Esquemático del NetSure 501 A50
Sistema de Fuente de Potencia en subrack de 19 Pulgadas NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51
Scheme 1
for 3P+N+PE/380V+SPD AC input
Signal Board
N Bar
Monitor
Note:
1. The AC distribution has 3 schemes, determined by user requirement.
230VAC
Appendix 3 Diagrama Esquemático
Scheme 2
Scheme 3
for 3P+PE/220V+SPD AC input
for 3P+N+PE/380V AC input
PE Bar
N Bar
Manual de Usuario
116