Case
Assembly
Wide vers. case
(power supply S)
Assembly
(power supply S)
Wide versions
Display
Keypad
Infrared receiver
Clock with backup battery
Buzzer
Clock
Operating conditions
Storage conditions
Front panel index of protection
Environmental pollution
PTI of insulating materials
Period of stress across the insulating parts long
Category of resistance to fi re
Class of protection against voltage surges category II
Type of action and disconnection
Construction of the control device
Classifi cation according to protection
against electric shock
Device designed to he hand-held or
integrated into equipment designed to
be hand-held
Software class and structure
Cleaning the front panel of the
instrument
Serial interface for CAREL network
Interface for repeater display
Maximum distance between interface
and display
Programming key
ir33 platform "connections" +030220447 - rel. 2.2 - 15.06.2010
plastic: dimensions 36x167x51 mm; mounting depth 40 mm
smooth, hard and indeformable panel: using screws from the front
drilling template: dimensions 29x138.5 mm; distance between fastening screws 153.5 mm
fastening screws: countersunk head with maximum thread diameter 3.9 mm
plastic
smooth, hard and indeformable panel
drilling template
fastening screws
digits: 3 digit LED
display: from -99 to 999
operating status: indicated with graphic icons on the display
8 silicone rubber buttons
available depending on the model
available depending on the model
available in all models
Error at 25 °C:
Error in the temperature range –10T60 °C:
Ageing:
Discharge time:
Recharge time:
-10T65 °C; <90% relative umidity non-condensing
-20T70 °C; <90% relative umidity non-condensing
assembly on smooth and indeformable panel with IP65 gasket
2, normal situation
printed circuits 250, plastic and insulating materials 175
category D and category B (UL 94-V0)
1B relay contacts (micro-disconnection)
electronic control device incorporated
to be integrated into class I appliances
no
class A
only use neutral detergents and water
External, available in all models
External, available in all models
10 m
Available in all models
dimensions: 39.4x183x45
mounting depth 40 mm
using screws from the front or brackets
dimensions: from 138.5x29 to150x31
distance between fastening screws: 165 mm or 153.5
countersunk head with maximum thread diameter 3.9 mm for 165 mm spacing
fl at head for 153 mm spacing, maximum thread diameter 3 mm
± 10 ppm (±5.3 min/year)
- 50ppm (-27min/year)
< ±5p pm (±2.7 min/year)
typically 6 months (8 months maximum)
typically 5 hours (< 8 hours maximum)
11