Powercompact; Dimensions; Electrical Specifi Cations - Carel ir33 platform Manual Del Usuario

Ocultar thumbs Ver también para ir33 platform:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

1.1 Dimensions

Appearance and ergonomics:
The appearance has been designed to fi t in harmoniously with the new lines of the refrigeration units.
The main characteristic is its compactness: the dimensions are in fact 167x 36 x75 mm in the standard version.
POWER COMPACT WIDE
AUX
dima di foratura
drilling template
Key:
1. drilling template 138.5 x 29 mm;
2. faston (spade) version + 8 mm
1.2 Electrical specifi cations
Power supply
Insulation guaranteed by the power
supply
Inputs
Type of probe
ir33 platform "connections" +030220447 - rel. 2.2 - 15.06.2010

1. POWERCOMPACT

183.4
153.5
165
voltage
model E:
230 V~ 50/60 Hz;
230 V~ 50/60 Hz, 16 A, 8 A, 8 A version;
model A:
115 V~ 50/60 Hz;
115 V~ 50/60 Hz, 16 A, 8 A, 8 A version;
model H:
115-230 Vac 50/60Hz
model 0:
12 V~ , 50/60Hz
12 Vdc, 12-18Vdc
voltage
model E, A, H:
insulation from very low voltage parts
insulation from relay outputs
model 0:
insulation from very low voltage parts
insulation from relay outputs
S1
NTC or PTC, depending on the model
S2
NTC or PTC, depending on the model
DI1
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S3
NTC or PTC, depending on the model
DI2
voltage-free contact, contact resistance < 10 ohm, closing current 6 mA
S4
NTC or PTC, depending on the model
Maximum distance between probes and digital inputs less than 10 m
Note: in the installation, keep the power supply and load connections separate from the probe, digital inputs, repeater display and supervisor
cables.
Std. Carel NTC
High temperature NTC
Std. Carel PTC (specifi c model)
1
Fig. 1.a
power
3 VA, 25 mA~ max
3 VA, 25 mA~ max
3 VA, 50 mA~ max
3 VA, 50 mA~ max
6 VA, 50mA~ max
4 VA, 300 mA~ max
TRADR4W012 transformer, 315 mA slow-blow fuse in secondary,
only use SELV power supply
power
reinforced.; 6 mm air, 8 mm surface; 3750 V insulation
basic; 3 mm air, 4 mm surface; 1250 V insulation
to be guaranteed externally by safety transformer
basic; 3 mm air, 4 mm surface; 1250 V insulation
10 kat 25 °C, range –50T90 °C
measurement error: 1 °C in the range –50T50 °C
3 °C in the range +50T90 °C
50 k at 25 °C, range –40T150 °C
measurement error: 1.5 °C in the range –20T115 °C
4 °C in the range outside of -20T115 °C
985  at 25°C, range -50T150 °C
measurement error: 2 °C in the range –50T50 °C
4 °C in the range +50T150 °C
7
POWER COMPACT STANDARD
167
64
75
8
2

Capítulos

Tabla de contenido
loading

Tabla de contenido