6.4. Protection configuration

6.5. Sensor management

Regulation of source 1, 2, 3 and 4
Used to configure the maximum and minimum regulation % at which the source will
function. This will be for the circulator pump in a geothermal source and for the fan in an
aerothermal source.
Defrosting of source 1, 2, 3 and 4
Only for sources configured as aerothermal.
1. Used to enable the defrost program of the aerothermal collector.
2. Used to configure the nominal DT in the conditions in which there is no frost. DT is the
difference between the outdoor air temperature and the temperature of the glycol at
the outlet of the source.
3. Used to configure the % increase of DT to start the defrost cycle.
4. Used to configure the glycol temperature at the collector outlet to end defrosting.
5. Used to configure a maximum time by which to end defrosting despite the configured
"T return" not having been reached.
External fault
Used to configure the NO/NC (normally open/closed) logic of the digital input of each
source to receive external alarm signals.
XXXXXX
1. Displays the type of sensor installed in each analogue input and their current value.
2. Used to enter a correction of the sensor readings.
Note: There are screens for all temperature probes.