4.
To stop the test and exit Test mode, press and hold the
Test (T) button again for at least 3 seconds (long press).
The module exits the test automatically after 5 minutes if
the Test (T) button is not pressed.
After the test the output returns to its original state.
Note:
The module exits Test mode automatically if the control
panel sends a command to switch the relay (for example an
alarm command) or if the control panel is reset.
Specifications
Electrical
Operating voltage
Current consumption
Standby
Active
Polarity sensitive
Number of relays
Relay contact rating
Isolation
Current consumption (isolation
active)
Isolation voltage
Minimum
Maximum
Reconnect voltage
Minimum
Maximum
Rated current
Continuous (switch closed)
Switching (short circuit)
Leakage current
Series impedance
Maximum impedance [1]
Between the first isolator and
the control panel
Between each isolator
Number of isolators per loop
Number of devices between
isolators
[1] Equivalent to 500 m of 1.5 mm
Mechanical and environmental
IP rating
Operating environment
Operating temperature
Storage temperature
Relative humidity
Colour
Material
Weight
Dimensions (W × H × D)
P/N 12-0201-501-4004-01 • ISS 21NOV23
17 to 29 VDC (4 to 11 V pulsed)
300 µA at 24 VDC
2.5 mA at 24 VDC
Yes
2 × latched relays (NC, C, NO),
combined
1A at 60 VDC or 5A at 250 VAC
(resistive load)
2.5 mA
14 VDC
15.5 VDC
14 VDC
15.5 VDC
1.05 A
1.4 A
1 mA max.
0.08 Ω max.
13 Ω
13 Ω
128 max.
32 max.
2
(16 AWG) cable.
IP30
−22 to +55°C
−30 to +65°C
10 to 93% (noncondensing)
White (similar to RAL 9003)
ABS+PC
220 g
109 × 88 × 40 mm
Protective housing
The module must be installed inside a protective housing that
complies with all applicable EN 62368-1 requirements
(protection against electric shock, fireproof, etc.).
In addition to the above, the protective housing must meet the
following specifications.
IP rating
Material
Weight [1]
[1] Excluding the module.
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Conformity
Notified/Approved body
Manufacturer
Year of first CE marking
Declaration of
Performance number
EN 54
Product identification
Intended use
Declared performance
[1] Certified installed inside the N-IO-MBX-1 DIN Rail Module Box
Min. IP30 (indoor installation)
Metal
Min. 4.75 kg
0370
Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2023
12-0201-360-0003 [1]
EN 54-17, EN 54-18
KE-IO3101-M
See the product Declaration of
Performance
See the product Declaration of
Performance
2012/19/EU (WEEE Directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: recyclethis.info.
3 / 28