*For applications where the electricity network may be either 115VAC or 230VAC, always choose the
cross-section recommended for 115VAC.
Always use cable markers with insulating collars in accordance with installation standards governing
AC network input connections.
The PE conductor (commonly called "earth", the green and yellow wire) of the AC source must be
connected to the charger on the terminal provided for the purpose, and this must be done before
connecting any other terminals.
Please refer to the relevant diagram in the appendix.
The rating of the upstream circuit-breakers should match the equipment's requirements.

4.2.3 Battery cable

The CPS2 charger is equipped with 4 output terminals:
K4: - BAT (minus set of batteries)
K5: +BAT D (plus start-up battery for marine-type applications)
K6: +BAT 1 (plus battery set 1)
K7: +BAT 2 (plus battery set 2)
Up to 3 metres, the cross-section of the battery cables should be at least equal to or greater than the values
provided in the table below:
www.Busse-Yachtshop.de
Minimum cross-section and type
of cable for 115VAC
3 x 1.5mm² HO7-VK
3 x 1.5mm² HO7-VK
3 x 2.5mm² HO7-VK
3 x 4mm² HO7-VK
CPS2DEA.DOC
Minimum cross-section and type
of cable for 230VAC
3 x 1.5mm² HO7-VK
3 x 1.5mm² HO7-VK
3 x 1.5mm² HO7-VK
3 x 2.5mm² HO7-VK
32