Special Operation; Installation; Introduction; Items Supplied - Cristec CPS Serie Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

This indicator lights steadily when the Floating
charge mode : "BOOST OFF" has been
selected
and
correctly.
This indicator flashes if Boost mode operation :
"BOOST ON" has been selected. This mode of
operation lasts for 6 hours ± 30 minutes before
the charger automatically switches to Floating
mode operation. At that moment, the indicator
changes to a fixed steady light.

2.2.4.3 Special operation

Special batteries
The factory settings are for standard use of
Lead/Antimony and Lead/Calcium batteries.
Refer to a professional installer for special settings to
match the battery manufacturer's specifications,
taking into account the special features of the

installation.

Electricity generating sets
The CRISTEC battery charger is designed for use
from an electricity generating set.
In certain circumstances, generating sets can generate
large over-voltage. Before connecting the charger,
check that the charger is compatible with the
generator: power, voltage, voltage surges, frequency,
current, etc...
3 Installation
3.1

INTRODUCTION

This section deals with matters relating to charger
installation.
Installation and operating the charger for the first time
must be taken by an electrician or professional
installer in accordance with the standards in force (in
the case of pleasure boats, comply with the
international standard ISO 13297).
The installer must take note of this operating manual
and must inform users of the matters relating to
installation and safety contained in section 5.
the
charger
is
functioning
CPSDED
3.2

ITEMS SUPPLIED

CRISTEC supply items include the following
elements :
1 metal case containing the battery charger
electronic functions,
the present documentation (operating manual).
3.3
ADDITIONAL SUPPLIES NECESSARY
FOR ELECTRICAL INSTALLATION
These items do not form part of CRISTEC supply.
Reference to additional supply items which are
necessary for correct operation of the charger are
defined in the following sections :
Any failure to comply with these provisions will
result in cancellation of the manufacturer's guarantee.
3.3.1 Cable connecting to the public mains
supply or to an electricity generating set
The cable connecting to the public mains supply or to
a generating set is supplied with the charger.
The PE conductor
green/yellow wire) of the ac source MUST be
connected to the charger on the terminal provided for
this purpose.

3.3.2 Battery connection cable

Up to 3 meters, cables connecting to the batteries
MUST have a cross-section equal to, or greater than,
the values shown in the table below :
Model
12V 06A 2,5 mm² HO7-VK
24V 03A 1,5 mm² HO7-VK
12V 10A
24V 05A 2,5 mm² HO7-VK
12V 12A
(commonly called
Type of terminal
Cross-section and
Cross-section of
type of battery
connection cables
diameter of the
End-fittings with
insulated sleeves
MUST be fitted
4 mm² HO7-VK
with standard NF
4 mm² HO7-VK
Page 17
"earth"
cable and
terminal hole
(in accordance
G63-023)
Tabla de contenido
loading

Este manual también es adecuado para:

Cps 12v 06aCps 24v 03aCps 12v 10aCps 24v 05aCps 12v 12a

Tabla de contenido