Watts FEBCO LF860 Serie Manual De Instalación Y Mantenimiento
Watts FEBCO LF860 Serie Manual De Instalación Y Mantenimiento

Watts FEBCO LF860 Serie Manual De Instalación Y Mantenimiento

Válvulas antirretorno de principio de presión reducida, conjuntos de detectores de presión reducida 21/2' – 10' (6.35 a 25.4 cm)
Ocultar thumbs Ver también para FEBCO LF860 Serie:
Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Installation, Maintenance, and Repair Manual
Series LF860 Large and LF866
Reduced Pressure Zone Assemblies
Reduced Pressure Detector Assemblies
2
" – 10"
1
2
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
WARNING
!
Need for Periodic Inspection/Maintenance: This product
must be tested periodically in compliance with local codes, but
at least once per year or more as service conditions warrant. If
installed on a fire suppression system, all mechanical checks,
such as alarms and backflow preventers, should be flow tested
and inspected in accordance with NFPA 13 and/or NFPA 25.
All products must be retested once maintenance has been
performed. Corrosive water conditions and/or unauthorized
adjustments or repair could render the product ineffective for
the service intended. Regular checking and cleaning of the
product's internal components helps assure maximum life and
proper product function.
WARNING
!
The installation and maintenance of backflow assemblies should
be performed by a qualified, licensed technician. Failure to do
so may result in a malfunctioning assembly.
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
Fittings such as end connectors intended to join alternative pipe
systems made from other materials (such as plastics) shall
also conform to the relevant dimensional and performance
requirements of the appropriate Australian, New Zealand, or joint
Australian–New Zealand Standard for the alternative pipe system.
LF860-OSY with Flood Sensor
Series LF860 and LF866 each include a sensor on the relief
valve to detect excessive discharge and trigger notification of a
potential flood event.
NOTICE
An add-on connection kit is required to activate the flood
sensor. Without the connection kit, the flood sensor is a passive
component that does not communicate with any other device.
(A retrofit sensor connection kit is also available for existing
installations. See "Add-on and Retrofit Sensor Connection Kits,"
for ordering details.)
NOTICE
Use of the flood sensor does not replace the need to comply with
all required instructions, codes, and regulations related to installation,
operation, and maintenance of this product, including the need to
provide proper drainage in the event of a discharge.
Watts
is not responsible for the failure of alerts due to connectivity
®
issues, power outages, or improper installation.
IS-F-860RP/RPDA
loading

Resumen de contenidos para Watts FEBCO LF860 Serie

  • Página 1 Australian, New Zealand, or joint Watts is not responsible for the failure of alerts due to connectivity Australian–New Zealand Standard for the alternative pipe system.
  • Página 2 Installation Guidelines Typical Installation NOTICE The flange gasket bolts for the gate valves should be Figure 1 retightened during installation as the bolts may have loosened due to storage and shipping. 1. Consult local codes for specific installation requirements and 12"...
  • Página 3 Service and Maintenance • Rinse all parts with clean water before reassembly. Relief Valve Disassembly • Do not use any pipe dope, oil, grease, or solvent on any parts 1. Detach the activation module, if installed, from the flood sensor. unless instructed to do so.
  • Página 4 MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT. USA: T: (800) 767-1234 • FEBCOonline.com Canada: T: (888) 208-8927 • FEBCOonline.ca Latin America: T: (52) 55-4122-0138 • FEBCOonline.com IS-F-860RP/RPDA 2348 980053 © 2023 Watts...
  • Página 5 (tels que les plastiques) doivent également être drainage approprié en cas d’évacuation. conformes aux exigences dimensionnelles et de performance de Watts n’est pas responsable de la défaillance des alertes due à ® la norme australienne, néo-zélandaise ou de la norme conjointe des problèmes de connectivité, à...
  • Página 6 Directives d’installation Installation typique A VIS Les boulons de joint d’étanchéité de bride pour les robinets- Figure 1 vannes doivent être resserrés pendant l’installation, car ils peuvent se desserrer lors du transport et de l’entreposage. 1. Consultez les codes locaux pour les exigences et restrictions 12 po (30,4 cm) min.
  • Página 7 Entretien et maintenance • Rincez toutes les pièces à l’eau propre avant le remontage. Démontage de la soupape de décharge • N’utilisez pas de pâte lubrifiante, d’huile, de graisse ou de solvant sur 1. Détachez le module d’activation, le cas échéant, du capteur d’inondation. une pièce à...
  • Página 8 ÊTRE ASSUMÉE, Y COMPRIS LES GARANTIES IMPLICITES DE QUALITÉ MARCHANDE ET D’APTITUDE À UN USAGE PARTICULIER, SERA LIMITÉE À UN AN À PARTIR DE LA DATE DE L’EXPÉDITION D’ORIGINE. É.-U. : Tél. : (800) 767-1234 • FEBCOonline.com Canada : Tél. : (888) 208-8927 • FEBCOonline.ca Amérique latine : Tél. : (52) 55-4122-0138 • FEBCOonline.com IS-F-860RP/RPDA 2348 980053 © 2023 Watts...
  • Página 9 (como plásticos) también deben cumplir con los requisitos dimensionales y de rendimiento relevantes del estándar Watts no es responsable de la falla de las alertas debido a ® australiano, neozelandés o conjunto australiano–Nueva Zelanda problemas de conectividad, cortes de energía o instalación...
  • Página 10 Pautas de instalación Instalación típica AVIS O Los pernos de la junta de la brida de las válvulas de Figura 1 compuerta deben volver a apretarse durante la instalación, ya que los pernos pueden haberse aflojado debido al almacenamiento y envío. 12"...
  • Página 11 Servicio y mantenimiento • Enjuague todas las piezas con agua limpia antes de volver a Desensamble de la válvula de alivio ensamblarlas. 1. Desconecte el módulo de activación, si está instalado, del sensor • No use lubricante para tuberías, aceite, grasa o solvente sobre ninguna de inundación.
  • Página 12 RENUNCIADA, INCLUYENDO LAS GARANTÍAS IMPLÍCITAS DE COMERCIABILIDAD E IDONEIDAD PARA UN PROPÓSITO PARTICULAR, TIENEN UNA DURACIÓN LIMITADA A UN AÑO A PARTIR DE LA FECHA DE ENVÍO ORIGINAL. EE. UU.: T: (800) 767-1234 • FEBCOonline.com Canadá: T: (888) 208-8927 • FEBCOonline.ca América Latina: T: (52) 55-4122-0138 • FEBCOonline.com IS-F-860RP/RPDA 2348 980053 © 2023 Watts...

Este manual también es adecuado para:

Febco lf866 serieFebco lf860-osy