8- Brake (Brake) [ 0% ]
Set the required brake value between 0 and 99%, compatibly with the
weight of the gate and the existing stresses.
9- Zone (zone) [ 0 ] (Advanced parameters ⇒ address 1)
Set the zone number between a minimum value of 0 and a maximum
value of 128. See paragraph 11 on "Serial connection".
10-Slow-down Distance (Cm. rall) [ 000 ](Advanced parameters ⇒address 3)
Set the required slow-down distance for opening and closing between 0
cm and 100 cm The 000 cm value does not carry out any slow-down.
NOTE: If a slow-down distance value other than 000cm is set, after the first
manoeuvre, power failure, the control panel carries out a complete ma-
noeuvre at reduced speed, in order to learn the length of gate stroke.
6.2) Logic Menu (logic. )
- TCA ( tca ) [ ON ]
ON
Activates automatic closing
OFF Excludes automatic closing
-
3 Steps (3 step) [ OFF ]
ON
Enables 3-step logic. A start impulse has the following effects:
door closed: ..............................................................................opens
on opening: ............................. stops and enters TCA (if configured)
door open: ............................................................................... closes
on closing: ......................................... stops and reverses movement
after stopping:...........................................................................opens
OFF Disables 3-step logic.
-
Opening Impulse lock (Ibl open) [ OFF ]
ON
The Start impulse has no effect during the opening phase.
OFF The Start impulse becomes effective during the opening phase.
-
Impulse lock TCA (ibl TCA ) [ OFF ]
ON
The Start impulse has no effect during the TCA dwell period.
OFF The Start impulse becomes effective during the TCA dwell period.
-
Pre alarm (pre-alarM) [ OFF ]
ON
The blinker comes on about 3 seconds before the motor starts.
OFF The blinker comes on at the same time as the motor starts.
-
Hold-to-run (hold-to-run ) [ OFF ]
ON
Hold-to-run operation: the manoeuvre continues as long as the
command key is kept pressed.
OFF Impulse operation: one impulse opens the gate if closed, and clos-
es it if open.
-
Rapid closing (fast cls ) [ OFF ]
ON
Closes the gate after photocell disengagement, before waiting for the
end of the TCA (automatic closing time) set.
OFF Command not entered.
-
Photocells on opening (photc. open) [ OFF ]
ON
In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.
OFF In case of obscuring, the photocells are active both on opening and
on closing. When a photocell is obscured on closing, it reverses the
motion only after the photocell is disengaged.
Master/Slave (Master) [ OFF ] (Advanced logics ⇒ address 12)
-
ON
The control panel is set as Master in a centralised connection (see
Paragraph 11).
OFF The control panel is set as Slave in a centralised connection (see
Paragraph 11).
Photocell test (test phot) [ OFF ] (Advanced logics ⇒ address 14)
-
ON
Activates photocell check (see fig. 7 to 14)
OFF Deactivates photocell check
-
Electric edge test (test bar) [ OFF ]
ON
Activates electric edge check (see fig. 7 to 14)
OFF Deactivates electric edge check
-
Gate-open or 2nd radio channel warning light (SCA 2ch) [ ON ]
ON
The output between terminals 12 and 13 is configured as Gate-open warn-
ing light, in this case the 2nd radio channel controls pedestrian opening.
OFF The output between terminals 12 and 13 is configured as 2nd radio
channel.
Fixed code (fixed code) [ OFF ] (Advanced logics ⇒ address 13)
-
ON
The receiver is configured for operation in fixed-code mode, see
paragraph on "Radio Transmitter Cloning".
OFF The receiver is configured for operation in rolling-code mode, see
paragraph on "Radio Transmitter Cloning".
-
Radio transmitter programming (radio prog) [ ON ]
(Advanced logics ⇒ address 15)
ON
This enables transmitter storage via radio:
1 – First press the hidden key (P1) and then the normal key (T1, T2,
T3 or T4) of a transmitter already memorised in standard mode by
means of the radio menu.
2 – Within 10s press the hidden key (P1) and the normal key (T1, T2,
T3 or T4) of a transmitter to be memorised.
INSTALLATION MANUAL
OFF This disables transmitter storage via radio.
6.3) Radio Menu (radio)
-
Add (add)
Allows you to add one key of a radio control device to the receiver memory;
after storage it displays a message showing the receiver number in the
memory location (from 01 to 64).
Add Start button (add start)
associates the required key to Start command
Add 2ch button (add 2ch)
associates the required key to 2nd radio channel
-
Read (read)
Checks one key of a receiver; if stored it displays a message showing
the receiver number in the memory location (from 01 to 64), and the key
number (T1, T2, T3 or T4).
-
Eliminate list (erease 64)
WARNING! Completely removes all memorised radio control devices
from the receiver memory.
-
Receiver code reading (RX code)
This displays the code entered in the receiver.
- W LINK (uk)
ON =
Enables remote programming of cards via a previously memorized W
LINK remote control.
It remains enabled for 3 minutes from the time the W LINK remote control
is last pressed.
Refer to the W LINK remote control's manual for the mapping of the
relevant keys.
OFF =
W LINK programming disabled.
Consult paragraphs 7/8/9/10 for further information concerning the
advanced functions of the Clonix incorporated receiver.
6.4) Language Menu (Language)
Allows you to set the language on the display programmer.
5 languages are available:
-
ITALIAN (TA)
-
FRENCH (FRA)
-
GERMAN (DEU)
-
ENGLISH (ENG)
-
SPANISH (ESP)
6.5) MENU DEFAULT (DEFAULT)
Restores the preset default values on the control unit. After restoring, a new
autoset operation must be carried out.
6.6) DIAGNOSTICS AND MONITORING
The display on the LEO-D-MA panel shows some useful information, both
during normal operation and in the case of malfunctions.
Diagnostics:
In the case of malfunctions, the display shows a message indicating which
device needs to be checked:
STRT
STOP
PHOT
FLT
SWO
SWC
PED
OPEN
CLS
BAR
TIME
In the case where an obstacle is found, the LEO-D-MA panel stops the door
and activates a reverse manoeuvre; at the same time the display shows the
"BAR" message.
Monitoring:
During the opening and closing phases, the display shows four digits sepa-
rated by a dot, for example 35. 4 0.
Figures are constantly updated during the manoeuvre and represent the
instant torque reached by motor 1 (35) and threshold torque (opening, clos-
ing, slow-down) set in the parameter menu (40).
The receiver exits the programming mode after 10s, other new trans-
mitters can be entered before the end of this time.
This mode does not require access to the control panel.
The transmitters can only be memorised using the appropriate Radio
menu.
= START input activation
= STOP input activation
= PHOT input activation
= FAULT input activation for checked photocells
= input activation OPENING LIMIT SWITCH
= input activation CLOSING LIMIT SWITCH
= input activation PEDESTRIAN
= OPEN input activation
= CLOSE input activation
= input activation SAFETY EDGE
= TIMER input activation