4. Compact Bio/Compact Bio Luxury boiler design
70
4.H Wiring system
General guidelines on the wiring systems of the boiler control, the boiler and its
accessories:
1.
A 230 V/50 Hz power system conforming to local standards and regulations
must be available in the boiler room.
2.
The wiring system must be terminated with a plug-in socket and a
protective conductor contact.
WARNING!
Using the socket without
a protective conductor contact
may result in electric shock!
3.
The wiring system must be installed in accordance with the electrical
diagram and local regulations concerning electrical safety.
4.
The device (boiler/control system) must be connected to an individual
system with an overcurrent protection and a residual current device.
NO OTHER EQUIPMENT MAY BE CONNECTED TO THE BOILER'S
ELECTRICAL SYSTEM!
5.
The wiring system may be installed and repaired by authorised personnel
only.
6.
Disconnect the power supply before servicing.
7.
The boiler temperature sensor must be installed and secured in a submersi-
ble sleeve in the water section. The remaining cable must be coiled and laid
in the external boiler casing or other safe location (secured against sliding
off from the sleeve).
8.
The cables should not be bent or broken and the insulation should not be
damaged.
9.
Do not allow water, moisture, dust and dirt inside the device, otherwise it
may result in short-circuit, electric shock, fire or damage.
10. Ensure proper ventilation of the device (control) and free air flow to the
vents and air circulation around the device.
11. The electrical equipment (control, distribution board, burner and sensors)
are intended for indoor installation.