ZONE PARAMETERS
Corrective measures
Regardless of the variables activated in the calculation of the Indoor Air Quality index,
corrective measures will be initiated when the status of the variable is Medium or Low and
ionization and/or ventilation are set to Auto. The activations per variable shall be:
PM
or PM
2.5
CO
. Ventilation will be activated when the "Controlled mechanical ventilation" parameter is
2
enabled.
TVOC. Ventilation will be activated when the "Controlled mechanical ventilation" parameter
is enabled.
Ventilation
The CO
and TVOC measurements made by the AirQ Sensor will activate all the device's
2
ventilation control outputs (0-10 V ext. ventilation, Airzone damper and AirQ Sensor relay
outputs), depending on its configuration:
Auto. (By default) Ventilation will be activated when the CO
falls within the ranges defined as Medium or Low.
Manual ON. Ventilation will remain active regardless of the CO
status.
Manual OFF. Ventilation will remain off regardless of the CO
6
. Ionization will be activated if AirQ Box devices are available.
10
or TVOC measurement status
2
or TVOC measurement
2
or TVOC measurement status.
2