Hitachi PC-AMTB Manual De Instalación Y Funcionamiento página 7

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11
Factory-supplied components
1 FACTORY-SUPPLIED COMPONENTS
Item
Multitenant Box
Connector wire <1>
Red
Connector wire <2>
White
Connector wire <3>
Red
Installation and
operation manual
2 gENERAL DATA
Item
Power supply
Rated power
Peak power consumption
1) Connected to type A models (*)
2) Connected to type B models (*)
Dimensions (HxWxD)
Weight (g)
Mounting conditions
Working range
Temperature
Humidity
3 INSTALLATION
PC-AMTB enclosure is furnished with side bored flanges in order to easily screw it to a wall or vertical surface. It can also be left lying
on a flat surface such as a false ceiling.
N O T E
• HITACHI cannot anticipate every possible circumstance that
might involve a potential hazard.
• Read carefully this document before performing the installation
work.
D A N g E R
• Do not install this device in places accessible to the
general public. Install it in enclosures or other places
which not are accessible.
• Do not connect power supply before the device installation
is correctly done. Always disconnect power supply from
the device before any maintenance or servicing action.
1
PMML0325A rev.0 - 07/2014
Description
Units
Description
V
24 VDC/VAC ±10%
W
2.3
W
4.7
W
7
mm
90x120x40
g
160
-
Indoor
ºC
0-60ºC
%
20-85% RH
Qty.
For allowing individual shutdown of indoor units in a
1
multiple indoor unit installation.
For the electrical connection between "H-LINK2"
1
connector of PC-AMTB and the "CN2" connector of
Red
For the electrical connection between "EV IN"
1
connector of PC-AMTB and the "CN11" connector of
White
For the electrical connection between "EV OUT"
connector of PC-AMTB and the EVI wire-end
1
previously connected to the "CN11" connector of
Red
1
Installation instructions of the device.
N O T E
• (*): Indoor unit models type A: All indoor units except B and
C type.
• Indoor unit models type B: RPI-(8.0/10.0)FSN3E.
• Indoor unit models type C: RPI-(16.0/20.0)FSN3PE, which
cannot be used with PC-AMTB.
C A U T I O N
• The device installation must be performed by qualified
professionals.
• Check to ensure that the field supplied electrical components
(mains power switches, circuit breakers, wires, connectors and
wire terminals) have been properly selected according to the
electrical data indicated on this document and they comply
with national and local codes. If it is necessary, contact with
your local authority in regards to standards, rules, regulations,
etc.
Purpose
Indoor unit PCB.
Indoor unit PCB.
indoor unit PCB.
loading