Installation flow sensor (FS)
M ount ball valves up- and down-
stream of the flow sensor.
Consider the correct installa-
tion point. Normally this is the
outlet pipe (colder pipe for heating,
warmer pipe for cooling). Please
note the type plate information (see
also page 19).
C onsider the correct flow direction.
This is indicated by an arrow on the
side of the flow sensor.
T he flow sensor can be installed in
any position (also „overhead").
Do not install at highest point of
piping to avoid air inside the flow
sensor.
Consider the dimensions of the
meter.
Installation of the ball valve
M ount ball valves up- and down-
stream of the meter.
M ount a ball valve with bore M10x1
for the temperature sensor instal-
lation.
F or symmetrical temperature sen-
sor installation, mount a second
identical ball valve.
Mounting heat/cooling energy meter
F lush the system thoroughly before
installing the meter.
C lose valves and release pressure.
D ismount the existing flow sensor
/ fitting.
U se only new and flawless sealing
material, no hemp or similar! Clean
sealing surfaces and check for
damage.
I nstall the new flow sensor accord-
ing to the correct flow direction and
installation position.
Turn heat computer to desired read-
ing position.
Supply
Return
Asymmetrical sensor installation for
zelsius® C5-IUF with one temperature sensor
integrated in the flow sensor
Consumer
Installation of the temperature sensors
The installation of the temperature
sensors should be preferably sym-
metrical and as direct installation.
D o not remove the temperatur sen-
sor if already mounted on the flow
sensor. This is also valid for all the
safety seals which are mounted on
the device as a standard.
S ensors resp. their type labels are
partly colour-coded
(according to the model):
Red = Inlet pipe of the plant
(warmer pipe for heating, colder
pipe for cooling)
Blue = Outlet pipe of the plant
(colder pipe for heating, warmer
pipe for cooling)
T he connecting cables may not be
buckled, extended or shortened!
The seal at the sensor installation
point on the flow sensor may not be
damaged.
R emove locking screw and seal at
the ball valve completely, if existing.
I f provided, attach the O-ring to
the installation aid (the 2nd O-ring
is only a spare O-ring). Using the
installation aid, insert the O-ring
into the installation point according
to DIN EN 1434 with a slight circular
motion.
Using the other end of the instal-
lation aid bring the O-ring into the
correct position.
Mounting with plastic adapter:
I nsert the 2 halves of the plastic
connector into the sensor's three
notches (grooves) and press them
together.
Use the mounting aid as position-
ing aid.
Supply
Return
Symmetrical sensor installation for
zelsius® C5-IUF
Consumer
17