Humidity sensor Error (only on +14°C/+16°C units)
In the event that the humidity sensor is broken or its connection is interrupted on the display the label [E8], is
visualised; the humidity control device is automatically deactivated.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows the label [E2].
The condenser fan keeps operating according to the value given to parameter "F8".
If the three probes are broken or disconnected, E0, E1, and E2 alternate on the display.
UNIT WITH BROKEN SENSOR PROBES DURING DEFROST
Room probe error
In the event that the chamber sensor probe is broken or the respective connection has been interrupted
during the defrost phase the function will be completed normally.
The string set with the parameter "d6" and the label [E0] will be visualised alternatively on the display.
Humidity sensor Error
In the event that the humidity sensor is broken or its connection is interrupted on the display the label [E8], is
visualised; the humidity control device is automatically deactivated.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows the label [E2].
The condenser fan keeps operating according to the value given to parameter "F8".
If the three probes are broken or disconnected, E0, E1, and E2 alternate on the display.
HIGH TEMPERATURE ALARM
The buzzer may be silenced by pressing the button
The visual alarm signal stays on until the temperature returns within the normal range.
LOW TEMPERATURE ALARM
The buzzer may be silenced by pressing the button
The visual alarm signal stays on until the temperature returns within the normal range.
HIGH AND LOW TEMPERATURE ALARMS MEMORIZED
If the room temperature exceeds the setpoint, the label [AH] and the
temperature reached alternate on the display.
Press up to display the duration of the event causing the alarm.
If the room temperature is below the setpoint, the label [AL] and the
temperature reached alternate on the display. The buzzer sounds.
Press down to display the duration of the event causing the alarm.
The defrost led blinking at high frequency indicates high or low temperature
alarm.
Pushing the enter button the type of alarm recorded will be visualised on the
flashing display.
Pushing the enter button the critical temperature recorded will be visualised
on the flashing display.