Endress+Hauser Levelflex FMP50 Manual De Instrucciones página 160

Radar de onda guiada
Ocultar thumbs Ver también para Levelflex FMP50:
Menú de configuración
Descripción
Selección
Información adicional
Texto libre
Navegación
Requisito previo
160
Seleccione la unidad para el valor linealizado.
Selección/entrada (uint16)
• 1095 = [tonelada corta]
• 1094 = [lb]
• 1088 = [kg]
• 1092 = [Ton]
• 1048 = [gal. (USA)]
• 1049 = [gal. (Imp.)]
• 1043 = [ft³]
• 1571 = [cm³]
• 1035 = [dm³]
• 1034 = [m³]
• 1038 = [l]
• 1041 = [hl]
• 1342 = [%]
• 1010 = [m]
• 1012 = [mm]
• 1018 = [ft]
• 1019 = [pulgadas]
• 1351 = [l/s]
• 1352 = [l/min]
• 1353 = [l/h]
• 1347 = [m³/s]
• 1348 = [m³/min]
• 1349 = [m³/h]
• 1356 = [ft³/s]
• 1357 = [ft³/min]
• 1358 = [ft³/h]
• 1362 = [gal. (USA)/s]
• 1363 = [gal. (USA)/min]
• 1364 = [gal. (USA)/h]
• 1367 = [gal. (Imp.)/s]
• 1358 = [gal. (Imp.)/min]
• 1359 = [gal. (Imp.)/h]
• 32815 = [Ml/s]
• 32816 = [Ml/min]
• 32817 = [Ml/h]
• 1355 = [Ml/d]
La unidad seleccionada se utiliza únicamente para fines de visualización. El valor medido
no se convierte en función de la unidad seleccionada.
La linealización distancia a distancia también puede realizarse; es decir una
linealización desde la unidad de nivel hasta otra unidad de longitud. Seleccione el
modo de linealización Lineal para este propósito. Para especificar la nueva unidad de
nivel, seleccione Opción Free text en Parámetro Unidad tras linealización e
introduzca la unidad en Parámetro Texto libre (→  160).
 Ajuste → Ajuste avanzado → Linealización → Texto libre
Unidad tras linealización (→  159) = Free text
Levelflex FMP50 FOUNDATION Fieldbus