ENG
Prerequisites
DANGER – Danger to life due to electric shock. Make sure that the unit is voltage-free.
•
All general requirements are met, see "General", Page 22.
Required tools and materials
•
Saw
•
Switch cabinet mill if necessary
•
Protective covers
Procedure
1.
Ensure that the switch cabinet has a protective cover to protect against chips.
2.
Prepare the cut-out according to Fig. 8 and Tab. 6.
•
To ensure IP protection category IP54, the cutting edges must be straight and the maximum bending of the switch
cabinet must be 1 mm.
3.
Remove burr from cutting edges.
4.
Remove chips and assembly waste from the switch cabinet.
5.
Snap the top filterfan/outlet fan into the cut-out.
The unit is now assembled and can be connected electrically.
Operating Manual | Top Filterfans / Top Exhaust Filter | – 230 / 115 V | 086150000
24/40