6.3.2. Selecting Suitable AC circuit Breaker
DANGER
DANGER
The general requirements for the selection of circuit breakers are determined by standards
and country specific provisions. In the following, generally applicable influencing factors to be
considered when selecting a suitable circuit breaker are listed:
Factors influencing the ampacity of the cable: type of cable used, ambient temperature
around the cable, type of cable routing, bundling of cables.
Other influences on dimensioning: loop impedance, mutual heating of circuit breakers,
ambient temperature at the circuit breaker, selectivity, type of connected device.
If these factors are ignored, it increases the danger of the circuit breaker tripping under normal
operating conditions.
Description
Grid Side
Backup Side
6.3.3. Grid and Backup Connection
Grid and Backup Connector Instructions:
1.
Disconnect the circuit breakers and secure against reconnection.
2. Dismantle the AC cable by 50mm.
3. Shorten L and N by 2mm each, so that the grounding conductor is 2 mm longer. This
ensures that the grounding conductor is the last to be pulled from the screw terminal in the
event of tensile strain.
© 2023 Maxeon Solar Technologies, Ltd. All rights reserved. | 547143 Revision B - June 2023
Specifications included in this document are subject to change without notice
The maximum allowable grid circuit breaker specification is 50 A when
the copper conductor cross section for grid connection is 10 mm
factors influencing the ampacity of the cable, other influences on
dimensioning must be considered. You should use APP (SunPower One
app) or installer platform (SunPower One installer dashboard) to select
correct setting if the grid circuit breaker specification is 32 A or 40 A,
otherwise it increases the danger of the circuit breaker tripping under
normal operating conditions.
The maximum allowable grid circuit breaker specification is 40 A when
the copper conductor cross section for grid connection must be 6 mm
(in some countries: 8 mm
of the cable, other influences on dimensioning must be considered
seriously. You should use APP (SunPower One app) or installer platform
(SunPower One installer dashboard) to select correct setting if the grid
circuit breaker specification is 32 A or 40 A, otherwise it increases the
danger of the circuit breaker tripping under normal operating conditions.
Max. Current
43.5 A
21.7 A
) and factors influencing the ampacity
2
Circuit Breaker Size for
RESERVE-INV-1-P5-L1-INT
32/40/50 A
32 A
and
2
2
34
loading