4.2 KICK START
4.3 INITIAL
VOLTAGE
SETTING
Figure 4.2 - Kick Start enabling
Soft-Starter SSW-07 offers a Kick Start function for loads that
present a large initial resistance to movement.
This function is enabled through the Kick Start DIP Switch. The
duration of the voltage pulse is set through the trimpot Kick Start
Time.
The voltage pulse applied is of 80 % Un during the programmed
trimpot Kick Start Time.
NOTE!
Use this function only for specific applications and where necessary.
Set the initial voltage to a value that the motor starts to run as soon
as the start command is given to the SSW-07.
Initial Voltage
Setting Trimpot
Figure 4.3 - Initial voltage setting
Chapter 4 - SettING the SSW-07
Kick Start Enabling
DIP Switch
The dot indicates
the factory default
setting
27