hager TYF642F Guia De Inicio Rapido página 2

Actuador de ventilo-convectores, 2 canales
Idiomas disponibles

Idiomas disponibles

the outputs switch into the position then active,
e.g. forced control (depending on programming).
• Switching outputs : on deactivation of the
manual mode, the output relays remain in their
current position.
Activating the permanent manual control mode
Keypad
operation
has
been
beforehand and is not disabled.
- Press the
key for at least 5 s.
LED
is on, LED A1 is flashing, permanent
manual control mode is activated.
Deactivating the permanent manual control
mode
The device is in the permanent manual control
mode.
- Press the
key for at least 5 s.
The
LED is off, the bus mode is on.
• Heating/cooling outputs : on deactivation of the
manual mode, the outputs switch into the position
then active, e.g. forced control (depending on
programming).
• Fan outputs : on deactivation of the manual mode,
the outputs switch into the position then active,
e.g. forced control (depending on programming).
• Switching outputs : on deactivation of the
manual mode, the output relays remain in their
current position.
Operating the outputs
In the manual control mode, the outputs can be
operated directly. Depending on programming, the
operation of switching one output may also affect
other outputs.
The device must in the permanent or temporary
manual control mode.
- Press the
key repeatedly until the desired
output
is
selected.
The LED of the selected output A1...A8 is flashing.
The ON /3 and the OFF / 4 LEDs indicate the
status.
- Output operation with the ON /3 or the OFF / 4
key.
• Heating/cooling outputs : opening or closing
the valve.
• Fan outputs : selecting the fan stage.
• Switching outputs : switching on or off.
The selected output switches on or off.
The ON /3 and the OFF / 4 LEDs indicate the
status.
H
• Depending on programming and selected
output, several outputs are switched at the
same time.
• Heating and cooling of a fan coil output are
never activated at the same time.
• When the heating or the cooling output is
active, at least the first fan stage is active as
well.
• Temporary manual control: after all outputs
have been selected one after another, the
device quits the manual control mode with
the next brief press.
Switching off all outputs
The device must in the permanent manual control
mode.
- Press the ALL OFF key.
All outputs are switched off.
Disabling individual outputs
The device must in the permanent manual control
mode.
- Press the
key repeatedly until the desired
output
is
selected.
The LED of the selected output A1...A8 flashes.
- Press the keys ON /3 and OFF / 4 simultane-
ously for at least 5 s.
The selected output is disabled.
All
status
LEDs
of
the
A1...A8 are flashing fast.
- Activate the bus mode (deactivate the permanent
manual control mode).
2
H
• A disabled output can be operated in the
manual control mode.
• If a disabled output is selected in the manual
control mode, the LEDs are flashing twice
briefly at intervals.
Re-enabling the outputs
programmed
The device must in the permanent manual control
mode.
- Press the
output
is
The
status
A1...A8 flashes twice briefly at intervals.
- Press the keys ON /3
ously for at least 5 s.
The LED of the selected output A1...A8 is flashing
slowly.
- Activate the bus mode (deactivate the permanent
manual control mode).
Information for qualified electricians
q
• Electric shock in case of accidental
• Electric shocks can be fatal.
• Before working on the device, cut out
Fitting and electrical connection
Installing the device
• Observe the admissible temperature range.
Ensure sufficient cooling.
• Snap the device onto a mounting rail in acc. with
EN 60715. The connecting terminals must be at
the top.
Connection diagram (Fig. 3)
L
N
selected
output
key repeatedly until the desired
selected.
LEDs
of
the
selected
and OFF / 4simultane-
contact with live parts.
the mains supply and cover up live
parts in the surroundings.
A1
A2
A3
A4
A5
A6
A7
A8
TYF642F
TYF642F
A1 A2 A3 A4 A5 A6 A7 A8
A1 A2 A3 A4 A5 A6 A7 A8
ALL OFF
ALL OFF
230-240V
AC 250 V
A1-A8 µ 10A AC1 230V
ON /
ON /
OFF /
OFF /
L
L
30V s
30V s
Bus
Connecting the device
Observe the admissible loads
G
Assignment of the outputs depends on the
projected mode of operation (tables 1, 2 and 3).
Control options (Tab. 1)
Mode
Function
1
2-pipe heating only
2
2-pipe cooling only
output
3
2-pipe heating/cooling, switch-over
object
4
4-pipe heating/cooling, switch-over
object
5
4-pipe heating/cooling, actuating
variable preset
G
Outputs that are not used for fan stage control
can be used for simple switching. Assignment
of output terminals see project design data.
1- Connect the bus line to the bus terminal 4.
2- Connect the mains supply 5.
3- Connect the fan coil units to the actuator outputs
as provided for in the project design.
H
• One fan coil output with up to six fan
stages: connection example in Fig. 3; output
assignment information in table 2, Fig. 4 and
Fig. 5.
• Two fan coil outputs with up to three fan
stages respectively: connection example in
Fig. 6; output assignment information in table
3, Fig. 7 and Fig. 8.
• Connection details for fan coil units can be
found in the documentation of these devices.
Output connection for 1 fan coil output (Tab. 2)
Mode A1
1
heating valve
2
cooling valve
3
heating/
cooling valve
4
cooling valve
5
cooling valve
TP / S
Single-channel
fan
N
N
hierarchical
switching
outputs (Fig. 4)
A3
A4
1
1
0
2
1
1
3
1
1
4
1
1
5
1
1
6
1
1
A2
A3...A8
-
fan stages
-
fan stages
-
fan stages
heating
fan stages
valve
heating
fan stages
valve
stage
pattern
with
current-sourcing
A5
A6
A7
A8
0
0
0
0
0
0
0
0
1
0
0
0
1
1
0
0
1
1
1
0
1
1
1
1
6LE004143A