The type of cable (H07‐VK, MX, etc.) should be defined by the installer according to the application type and the
enforceable standards.
For applications where the electricity network may be either 115VAC or 230VAC, always choose the cross section
recommended for 115VAC.
Always use cable markers with insulating collars in accordance with installation standards governing AC network input
connections.
The rating of the upstream circuit‐breakers should match the equipment's requirements.
Mounting of AC supply connector
The alternative input is absolutely made using a WAGO connector type WINSTA reference770‐103 (not supplied for
OEM versions).
Remarks :
The YPOWER chargers are working as soon as they are connected (connected and supplied AC network cable)
The YPOWER chargers are stopped as soon as they are not anymore under voltage (disconnected AC network cable or
circuit breaker of the installation in OFF position).
25