No: 24049 – 04/19 rev. 4
Catalog Numbers • Les Numéros de Catalogue • Los Números de Catálogo: DSW-301/DSW-301-347/DSW-302/DSW-302-347
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)
DSW-301
DSW-302
The DSW Dual Technology Multi-Way Wall Switch sensors combine advanced passive infrared (PIR) and ultrasonic technologies into
one unit. The combined technologies help to eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load ON, and hold it ON as long as either or both technologies detect occupancy.
It allows for up to 4 sensors to be connected to the same circuit. The first sensor to detect occupancy will turn ON all the lights that are
connected to the same circuit. After the room is unoccupied, the last sensor that detected occupancy turns OFF all the lights once the
time delay has expired. The occupant can turn OFF the load at any time by pressing the ON/OFF button of any sensor that is connected
to the circuit. A "walk-through" mode can turn lights OFF after only 3 minutes if no activity is detected after 30 seconds following an
occupancy detection.
The DSW-301 has one relay and one ON/OFF button. The DSW-302 contains two relays and two ON/OFF buttons to allow control of one or
two loads independently. Pressing a button toggles the state of the corresponding relay. Optional Neutral is also available on all models.
DSW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if
the area is occupied. In the DSW-302, light level only affects the load on Relay 2. Users can override this function by pressing the
ON/OFF button. See the Light Level Adjustment section.
Turning Load(s) ON (ON Mode)
The relays are programmed independently for either Auto ON or Manual ON. In either mode, the load can be turned ON or OFF using
the ON/OFF button.
Manual ON
DIP 8 ON for Relay 1
DIP 9 ON for Relay 2
Auto ON
DIP 8 OFF for Relay 1
DIP 9 OFF for Relay 2
DSW-301-347
DSW-302-347
DESCRIPTION AND OPERATION
With an ON Mode DIP switch in the ON position, the occupant must press the ON/OFF button to turn ON
the load. The sensor keeps the load ON until no motion is detected for the selected time delay. There is a
30 second re-retrigger delay. If occupancy is detected during the delay, the sensor turns the load back ON.
After the re-trigger delay elapses the ON/OFF button must be pressed to turn ON the load.
With an ON Mode DIP switch in the OFF position, the load turns ON and OFF automatically based on
occupancy. If the load is turned OFF manually, Presentation Mode operation applies. This prevents the load
from turning ON automatically after it was deliberately turned OFF. Pressing the button to turn lights ON
returns the sensor to Auto ON mode.
Wattstopper
Dual Technology Multi-Way Wall Switch Occupancy Sensor
Interrupteur mural multiple à double technologie Détecteurs de mouvement
Interruptor de pared de múltiples vías con tecnología doble Sensores de ocupación
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltages:
DSW-301 & DSW-302 ...................................... 120/277 VAC, 50/60 Hz
DSW-301-347 & DSW-302-347 ...............................347 VAC, 50/60 Hz
Load Limits for relay 1:
@120 VAC ................ 1000W tungsten, ballast, E-ballast, LED, 1/4 HP
@277 VAC ................................ 1200W ballast, E-ballast, LED, 1/4 HP
@347 VAC ................................................ 1500W ballast, LED, 1/4 HP
Load Limits for relay 2:
@120 VAC .................. 800W tungsten, ballast, E-ballast, LED, 1/6 HP
@277 VAC ................................ 1200W ballast, E-ballast, LED, 1/6 HP
@347 VAC ................................................ 1500W ballast, LED, 1/6 HP
Time Delay Adjustment ......................................................... 5 to 30 minutes
Walk-Through Mode ...............................3 minutes if no activity after 30 sec.
Test Mode ...................................................... 10 min. with 5 -sec. time delay
PIR Adjustment ............................................................................High or Low
Ultrasonic Adjustment ........................................... Minimum to Maximum, Off
Frequency ...................................................................................40 kHz
Light Level Adjustment .............................................................. 8fc to 180+fc
Alerts .................................................................. Selectable Audible & Visual
Optional Neutral .............................................................................All models
Multi-Way Capability .......................................................................All models
Terminal screw torque .................................................... 16 lbf-in (18 kgf-cm)
®
SPECIFICATIONS
Tabla de contenido
loading

Resumen de contenidos para LEGRAND Wattstopper SW-301

  • Página 1 Wattstopper ® Dual Technology Multi-Way Wall Switch Occupancy Sensor Interrupteur mural multiple à double technologie Détecteurs de mouvement Interruptor de pared de múltiples vías con tecnología doble Sensores de ocupación No: 24049 – 04/19 rev. 4 Installation Instructions • Instructions d’Installation • Instrucciones de Instalación Catalog Numbers •...
  • Página 2 Model # Relay Default ON DIP switch Setting Mode DSW-301 Manual ON DSW-302 Auto ON Manual ON Time Delays The DSW sensor holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP switch settings.
  • Página 3 COVERAGE PATTERNS Top View Coverage testing has been performed according to the NEMA WD 7 guideline. For best performance, use in spaces not larger than 18’ x 15’. Major motion Major motion PIR Sensor Minor motion Minor motion Ultrasonic The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree field of Coverage Coverage view.
  • Página 4 DSW-301 and DSW-301-347 Wiring DSW-302 and DSW-302-347 Bi-Level Wiring DSW-302 and DSW-302-347 Dual Circuit Wiring Neutral Black Primary Black Primary Line Line 1 Black Line Load Load Load Blue Yellow Blue Yellow Line 2 Yellow Secondary Secondary Brown Brown Load Load Neutral Green...
  • Página 5: Dip Switch Settings

    SENSOR OPERATING MODES Sensor #1 Sensor #2 Light Fixture Auto-ON Auto-ON The load turns ON and OFF automatically based on occupancy detection by either one of the sensors. The sensors keep the load ON until no motion is detected and will use the time delay of the sensor with the lowest value.
  • Página 6: Cover Plates

    2. Verify that the sensor is mounted at least six feet (2 meters) away from any heating/ventilating/air conditioning device that may cause false detection. Verify that there is no significant heat source (such as a high wattage light bulb) mounted near the sensor. 3.
  • Página 7 INSTRUCTIONS EN FRANÇAIS DESCRIPTION ET FONCTIONNEMENT CARACTÉRISTIQUES DE L’UNITÉ Tensions : Les détecteurs interrupteurs muraux multiples à DSW-301 & DSW-302 ............. 120/277 VCA, 50/60 Hz double technologie DSW allient les technologies DSW-301-347 & DSW-302-347 ............. 347 VCA, 50/60 Hz de l’infrarouge passif (IRP) et des ultrasons en une Charges maximales pour le relais 1 : seule unité.
  • Página 8 Test/20 min. Le mode test, avec une temporisation courte de 5 secondes, est lancé lorsque les interrupteurs DIP 1 (DIP 1 & 2 OFF) et 2 sont ARRÊT. Il s’annule automatiquement au bout de dix minutes ou lorsque vous paramétrez une temporisation fixe.
  • Página 9 RÉGLAGES Réglage du détecteur Retirez la plaque murale. Retirez le cache du bouton en serrant fermement et simultanément les parties supérieures de l’ensemble bouton. Retirez-le doucement de l’unité. Lorsque les réglages sont terminés, reposez le cache du bouton en insérant ses charnières dans les ergots de l’unité principale, puis serrez les parties supérieures du bouton tout en le poussant dans l’unité.
  • Página 10 MULTI-VOIES La fonction de multi-voies est disponible sur tous les modèles. Les détecteurs peuvent facilement être connectés les uns aux autres pour le contrôle pratique d’une même charge. Si vous effectuez ce type de câblage, utilisez uniquement des détecteurs de la série 300. La fonction de multi-voies des détecteurs de la série 300 est incompatible avec les modèles plus anciens.
  • Página 11 MODES DE FONCTIONNEMENT DU DÉTECTEUR Détecteur 1 Détecteur 2 Luminaire MARCHE MARCHE La charge est automatiquement ACTIVÉE et DÉSACTIVÉE en fonction de la détection d'une présence automatique automatique par l'un des détecteurs. Les détecteurs garderont la charge allumée jusqu’à ce qu’il n’y ait plus de mouvement et utiliseront le délai du détecteur avec la temporisation la plus courte.
  • Página 12 CACHES Les interrupteurs muraux de la série DSW de Wattstopper peuvent être montés derrière des caches d’interrupteur de style Decorator aux normes du secteur. Les caches ne sont pas inclus. Les unités sont disponibles dans les couleurs suivantes, indiquées par le suffixe final du numéro de référence (montré ici entre parenthèses) : Blanc (-W), Amande légère (-LA), Ivoire (-I), Gris (-G), Noir (-B).
  • Página 13: Descripción Y Funcionamiento De La Unidad

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN Y FUNCIONAMIENTO DE ESPECIFICACIONES LA UNIDAD Voltajes: Los sensores del interruptor de pared de múltiples DSW-301 y DSW-302 ............120/277 V CA, 50/60 Hz vías con tecnología doble DSW combinan las DSW-301-347 y DSW-302-347 ..........347 V CA, 50/60 Hz tecnologías infrarroja pasiva (PIR) avanzada y la Límites de carga para el relé...
  • Página 14: Diagramas De Cobertura

    Prueba/20 min. Se configura un modo de prueba con una demora de tiempo breve de cinco segundos cuando los conmutadores selectores para bascular 1 y 2 están apagados. Se cancela automáticamente (Conmutador selector para después de diez minutos o cuando se configura una demora de tiempo fija. Cuando termina el bascular 1 y 2 OFF) modo de prueba, el sensor asume una demora de 20 minutos.
  • Página 15: Instalación

    Cómo enmascarar una lente Vista superior Se proporciona una cinta adhesiva opaca para que se puedan enmascarar secciones Movimiento Movimiento mayor mayor de las lentes del PIR. Puede eliminar la cobertura en áreas no deseadas. Dado que el Movimiento Movimiento menor menor enmascaramiento quita franjas de cobertura, tenga esto en cuenta al resolver problemas...
  • Página 16: Cableado Neutral Opcional

    Cableado de DSW-301 y DSW-301-347 DSW-302 y DSW-302-347 DSW-302 y DSW-302-347 Cableado de dos niveles Cableado de dos circuitos Neutro Negro Carga Rojo Línea Negro Carga Rojo Negro Rojo Línea 1 Línea Carga principal principal Azul Amarillo Azul Amarillo Amarillo Línea 2 Carga Marrón...
  • Página 17: Configuración Del Conmutador

    CONFIGURACIÓN DEL CONMUTADOR Modo de Botones de Encendido/Apagado encendido Relé 1 Tiempo Modo de Relé 1 Relé 2 de retardo activación Relé 2 Alerta audible Tiempo de retardo Habilitado Prueba/20 min. Desactivado Potenciometro 5 minutos de ajuste de 15 minutos sensibilidad Modo de encendido del relé...
  • Página 18: Placas De La Cubierta

    No. 24049 – 04/19 rev. 4 © Copyright 2019 Legrand All Rights Reserved. 800.879.8585 © Copyright 2019 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2019 Legrand Todos los derechos reservados.