Functions
a. ON DELAY
Un
Trigger
T
When the supply voltage is applied, the time delay T begins. When the timing is
complete, the relay closes and this condition continues until the supply voltage is
disconnected.
ON DELAY with Inhibit
Un
Trigger
t1
T = t1 + t2
If the control contact is closed and the supply voltage is connected, the relay is
opened and timing does not start until the control contact opens.
When the timing is complete, the relay closes. If the control contact is closed during
timing, the timing is interrupted and continues only after the control contact opens.
b. INTERVAL ON
Un
Trigger
T
After supply voltage relay closes and starts the delay time T. After the end of the
timing relay opens and this state lasts until the supply voltage is disconnected.
INTERVAL ON with Inhibit
Un
Trigger
t1
T = t1 + t2
If the control contact is closed and the supply voltage is connected, the relay will close
and the timing will start only after the control contact has been opened.
When the timing is complete, the relay opens. If the control contact is closed during
timing, the timing is interrupted and continues only after the control contact opens.
c. FLASHER - ON fi rst
Un
Trigger
T
After supply voltage relay closes and starts the delay time T. After the end of the timing
relay opens and again runs delay time T. When the timing is complete, the relay closes
again and the sequence is repeated until the supply voltage is disconnected. If the
control contact is closed during timing, this does not aff ect the operation of the cycler.
FLASHER - OFF fi rst
Un
Trigger
T
T
If the control contact is closed during timing; this does not aff ect the operation of the
cycler. If the control contact is closed and the supply voltage is connected, the cycler
starts with a pause (relay open).
T
t2
<T
T
t2
T
T
T
T
T
T
T
d. MEMORY LATCH
Un
Trigger
When the supply voltage is applied, the relay is open. When the control contact
is closed, the relay closes. The status does not change when the control contact is
opened. When the control contact is closed again, the relay opens. Each time the
control contact is closed, the relay changes status.
e. OFF DELAY
Un
Trigger
When the supply voltage is applied, the relay is open. When the control contact is
closed, the relay closes. When the control contact opens, the time delay T begins. If
the control contact is closed during timing, the time is reset and the relay remains
closed. When the control contact opens, the time delay T starts again and opens when
the relay closes.
f. SINGLE SHOT
Un
Trigger
When the supply voltage is applied, the relay is open. When the control contact is
closed, the relay closes and the time delay T begins. Closing the control contact during
timing is ignored.
g. WATCHDOG
Un
Trigger
When the supply voltage is applied, the relay is open. When the control contact
is closed, the relay closes and the time delay T begins. Closing the control contact
during timing triggers a new time delay T - the relay closing time is thus increased.
h. PULSE GENERATOR 0.5s
Un
Trigger
After the supply voltage has been applied, the time delay T begins. When the timing
is complete, the relay closes for a fi xed time (0.5s).
PULSE GENERATOR 0.5s with Inhibit
Un
Trigger
t1
T = t1 + t2
After supply voltage starts the time delay T. By closing timing of the control contact
during timing is suspended. When the control contact opens, the time interval is
completed and the relay closes for a fi xed time (0.5s).