SAFE logic= 2 - Input configured as Phot op (photocell active during opening only). (fig.O, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during closing. During opening, stops
motion for as long as the photocell beam stays broken. If not used, leave jumper inserted.
SAFE logic= 3 - Input configured as Phot op test (tested photocell active during opening only (fig.O, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during closing. During opening, stops motion for as long as the photo-
cell beam stays broken.
SAFE logic= 4 - Input configured as Phot cl (photocell active during closing only). (fig.O, ref.1).
Enables connection of devices not equipped with supplementary test contacts. In the event beam is broken, photocell operation is disabled during opening. During closing, move-
ment is reversed immediately. If not used, leave jumper inserted.
SAFE logic= 5 - Input configured as Phot cl test (tested photocell active during closing only (fig.O, ref.2).
Switches photocell testing on at start of operation. In the event beam is broken, photocell operation is disabled during opening. During closing, movement is reversed immediately.
SAFE logic= 6 - Input configured as Bar (safety edge). (fig.O, ref.3).
Enables connection of devices not equipped with supplementary test contacts. The command reverses movement for 2 sec.. If not used, leave jumper inserted.
SAFE logic= 7 - Input configured as Bar (tested safety edge (fig.O, ref.4).
Switches safety edge testing on at start of operation. The command reverses movement for 2 sec.
SAFE logic= 8 - Input configured as Bar 8k2 (fig.O, ref.5). Input for resistive edge 8K2.
The command reverses movement for 2 sec..
14) SAFETY DEVICES
Note: only use receiving safety devices with free changeover contact.
14.1) TESTED DEVICES Fig. O
14.2) CONNECTION OF 1 PAIR OF NON-TESTED PHOTOCELLS FIG. H
15) CALLING UP MENUS: FIG. 1
15.1) PARAMETERS MENU (PARA ) (PARAMETERS TABLE "A")
15.2) LOGIC MENU (LOGIC) (LOGIC TABLE "B")
15.3) DEFAULT MENU (default)
Restores the controller's DEFAULT factory settings. Following this reset, you will need
to run the AUTOSET function again.
15.4) LANGUAGE MENU (language)
Used to set the programmer's language on the display.
(
)
15.5) STATISTICS MENU
STAT
Used to view the version of the board, the total number of operations (in hundreds),
the number of transmitters memorized and the last 30 errors (the first 2 digits indicate
the position, the last 2 give the error code). Error 01 is the most recent.
(
15.6) PASSwORD MENU
PASSWORD
Used to set a password for the board's wireless programming via the U-link network.
With "PROTECTION LEVEL" logic set to 1,2,3,4, the password is required to access the
programming menus. After 10 consecutive failed attempts to log in, you will need to
wait 3 minutes before trying again. During this time, whenever an attempt is made to
log in, the display will read "BLOC". The default password is 1234.
16) OPENING DIRECTION REVERSAL (FIG. N1)
If the "op.dir.rev. " logic is on 1 the opening direction is reversed in comparison with the
standard operation and the limit switches are interpreted the opposite way.
TABLE "A" - PARAMETERS MENU - (PARA )
Parameter
min.
max.
10
300
OPEN WORK. T
10
300
CLS WORK. T
0
180
TCA
TRF. L GHT.
1
180
CLR. T
PARTIAL
3
300
OPENING
0
250
Maintenance
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
TABLE "B" - LOGIC MENU - (LOGIC)
Logic
Definition
Automatic Closing
TCA
Time
Fast closing
FAST CLS.
Step-by-step
STEP-BY-STEP
movement
MOVEMNT
20 -
SP 3500
INSTALLATION MANUAL
)
Default
Personal
Definition
300
Opening operation time [s]
300
Closing operation time [s]
40
Automatic closing time [s]
Time-to-clear traffic light
40
zone [s]
5
Partial opening time[%]
Programming number of
0
operations for maintenance
threshold [in hundreds]
Cross
out
Default
setting
used
0
0
1
0
0
1
0
1
0
2
Safety input configuration
17) CONNECTION wITH EXPANSION BOARDS AND UNIVERSAL HANDHELD
PROGRAMMER VERSION> V1.40 (Fig. B) Refer to specific manual.
18) RADIO-RECEIVER (Fig. I)
The board comes ready for connection of removable radio-receiver.
The receiver's channel 1 controls input IC1.
The receiver's channel 2 controls terminals 26-27.
19) U-LINK OPTIONAL MODULES
Refer to the U-link instructions for the modules.
The use of some models causes lowered radio capacity. Adjust the system using an
appropriate antenna tuned to 433MHxz.
20) OPPOSING SLIDING DOORS (FIG.R)
REFER TO THE INSTRUCTIONS FOR THE U-LINK MODULES
21) RESTORING FACTORY SETTINGS (Fig.S)
wARNING: this operation will restore the control unit's factory settings and all transmit-
ters stored in its memory will be deleted.
WARNING! Incorrect settings can result in damage to property and injury to people
and animals.
- Cut off power to the board (Fig.S ref.1)
- Open the Stop input and press the - and OK keys together (Fig.S ref.2)
- Switch on the board's power (Fig.S ref.3)
- The display will read RST; confirm within 3 sec. by pressing the OK key (Fig.S ref.4)
- Wait for the procedure to finish (Fig.S ref.5)
- Procedure finished (Fig.S ref.6)
22) wIRING DIAGRAM OF THE ONBOARD CONTROLLER FIG. P-Q
Maximum motor operation time, during opening.
Set the operation time so that it's slightly longer than the complete operating cycle time.
The value is changed by the Autoset cycle, adapting it to the operation time detected
Maximum motor operation time, during closing.
Set the operation time so that it's slightly longer than the complete operating cycle time.
The value is changed by the Autoset cycle, adapting it to the operation time detected
Waiting time before automatic closing.
Time-to-clear for the zone run through by traffic controlled by the traffic light.
Partial opening time following the activation of the PED pedestrian control. It must be less
than the opening work time.
Allows you to set a number of operations after which the need for maintenance will be reported
on the AUX output configured as Maintenance or Flashing Light and Maintenance .
Logic not enabled
Switches automatic closing on
Logic not enabled
Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
Inputs configured as Start E, Start I,
Ped operate with 4-step logic.
Inputs configured as Start E, Start I,
Ped operate with 3-step logic. Pulse
during closing reverses movement.
Inputs configured as Start E, Start I,
Ped operate with 2-step logic. Move-
ment reverses with each pulse.
Description
Optional extras
step-by-step mov.
2 STEP
3 STEP
CLOSED
OPENS
OPENS
DURING
CLOSING
OPEN
CLOSES
CLOSES
DURING
STOP + TCA STOP + TCA
OPENING
AFTER STOP
OPENS
OPENS
4 STEP
OPENS
STOPS
CLOSES
OPENS