ELECTRICAL WIRING
Dip Switch Setting
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SWO1 is used to set capabilities of main and sub indoor units as well as indoor unit; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Definition and description of SW01
SW01_1
Address of wire
SW01_2
controlled indoor unit
SW01_3
SW01_4
SW01_5
Capability of indoor unit
SW01_6
SW01_7
SW01_8
(B) Definition and description of SW03
SW03_1
Address of setting
mode
SW03_2
Code-set indoor unit
~
address and centralized
SW03_8
controller address
Note :
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller = communication address + 0 or + 64.
SW03_ 2 = OFF, address of centralized controller = communication address + 0 = communication address SW03_ 2 = ON,
address of centralized controller = communication address + 64 (applies when centralized controller is used and there
are more than 64 indoor units)
• To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1 = ON and SW03_ 2 = OFF;
SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are address codes which are set according to actual
address.
• Address setting function of wired controller for ultrathin card machine is disabled.
31-5000579 Rev. 2
[1]
[2]
[3]
[4]
Address of wire controlled indoor unit (group address)
0
0
0
0
0# (wire controlled main unit) (default)
0
0
0
1
1# (wire controlled sub unit)
0
0
1
0
2# (wire controlled sub unit)
0
0
1
1
3# (wire controlled sub unit)
0
1
0
0
4# (wire controlled sub unit)
0
1
0
1
5# (wire controlled sub unit)
•••
•••
•••
•••
•••• •••
1
1
1
1
15# (wire controlled sub unit)
[5]
[6]
[7]
[8]
Capability of indoor unit
0
0
0
0
0.6HP (MVAO005ME2AA)
0
0
0
1
0.8HP (MVAO007ME2AA)
0
0
1
0
1.0HP (MVAO009ME2AA)
0
0
1
1
1.2HP (MVAO012ME2AA)
[1]
0
1
[2]
[3]
[4]
[5]
[6]
[7]
[8]
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
•••
•••
•••
•••
•••
•••
•••
0
1
1
1
1
1
1
1
0
0
0
0
0
0
1
0
0
0
0
0
1
1
0
0
0
0
1
0
•••
•••
•••
•••
•••
•••
•••
1
1
1
1
1
1
1
Address setting mode
Automatic setting (default)
Code-set address
Address of indoor unit
Address of centralized controller
0# (Default)
0# (Default)
1#
1#
2#
2#
•••
•••
63#
63#
0#
64#
1#
65#
2#
66#
•••
•••
63#
127#
23