INSTALLATION INSTRUCTIONS
1. Select the following places to install indoor units.
(1) Where there is enough room for the machine above the ceiling;
(2) Where the drainpipes can be well arranged;
(3) Where the distance between the air outlet port of the machine and the floor is not more than 9ft (2.7m);
(4) Where air inlet & outlet of the indoor units are not blocked;
(5) Where it is hard enough to bear the weight of the unit;
(6) Where there are no television, piano and other valuables under the indoor units as to avoid condensate dropping
down, causing damage.
(7) Where it is over 3.3ft (1m) away from the television and radio as to avoid the disturbance from television and radio.
(8) Select the indoor unit around (such as the ceiling of the installation of indoor units sandwich) dry bulb temperature
below 86°F(30°C) and relative humidity below 80% of the place. If the unit is running in a high humidity environment
above the above conditions, there may be water drops. Please add 0.4 ~0.8 inch (10~20mm) insulation material
(foamed polyethylene or equivalent) to the unit as well as piping and drain. When the insulation material exceeds 0.4
inch (10mm), please press to fit into the ceiling opening.
(9) The indoor unit is not affected by external invasions. Return air is not recommended at the door, window, if there is
no choice to keep closed, off the window, while saving energy can effectively reduce the air conditioning operation
exception.
Installation Space:
• Ensure there is adequate space for installation and maintenance (refer
to the following drawings).
• The installation height should be kept within 9ft (2.7m). Warm air is
more difficult to blow down to the floor so avoid installing more than 9
feet high.
3.9in
(100mm)
Space required for installation (unit: in(mm))
12
41.3in (1050mm)
Air supply
angle range
Outside the outlet can not
have obstacles such as
chandeliers, screens and so on
3.9in
(100mm)
3.9in
(100mm)
22in(560mm)
Suction
inlet
31-5000579 Rev. 2