INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
CAUTION: For propane/LP
gas, make sure external regula-
tor has been installed between
propane/LP supply and heater.
See guidelines under Connect-
ing to Gas Supply, page 10.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage heater regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas, or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply a noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.
12
All manuals and user guides at all-guides.com
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
2. Pressurize supply piping system by either
3. Check all joints from gas meter for natu-
4. Correct all leaks at once.
Equipment
Shutoff Valve
Propane/LP
Supply Tank
www.desatech.com
ure 14).
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas, or using compressed air.
ral or propane/LP supply to equipment
shutoff valve (see Figure 15 or 16). Apply
a noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.
Figure 14 - Equipment Shutoff Valve
Control Valve Location
Gas Meter
Equipment Shutoff Valve
Figure 15 - Checking Gas Joints for
Natural Gas
Control Valve Location
Equipment Shutoff Valve
Figure 16 - Checking Gas Joints for
Propane/LP Gas
Open
Closed
110720-01M