WIKA PSD-3 Serie Manual De Instrucciones página 24

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

6. Commissioning, operation
6.5 Parameters
Parameter Description
EN
SP1/SP2
Hysteresis function: Switch point switching output (1 or 2)
FH1/FH2
Window function: Window high switching output (1 or 2)
RP1/RP2
Hysteresis function: Reset point switching output (1 or 2)
FL1/FL2
Window function: Window low switch output (1 or 2)
EF
Extended programming functions
RES
Return the set parameter to the factory settings
DS1/DS2
Switch delay time, which must occur without interruption before any electrical signal change occurs (SP1 or SP2)
DR1/DR2
Switch delay time, which must occur without interruption before any electrical signal change occurs (RP1 or RP2)
OU1
Switching function switching output (1 or 2)
OU2
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
UNIT
Unit switching
0SET
Offset adjustment (3 % of span)
DISM
Display value in display mode
ACT = actual pressure value; LOW, HIGH = minimum, maximum pressure value OFF = display off;
SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,
SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2
DISU
Display update 1, 2, 5, 10 updates/second
DISR
Rotate display indicator by 180°
RHL
Clear the Min- and Max-value memories
PAS
Password input, 0000 = no password
Password input digit by digit
TAG
Input of a 16-figure alphanumeric measuring point number
24
WIKA operating instructions pressure switch, model PSD-3x
Tabla de contenido
loading

Este manual también es adecuado para:

Psd-30

Tabla de contenido