11.1 Technical data
uncertainty values are determined for temp. range 18...28ºC
and humidity <75%
"m.v." means a standard measured value.
True RMS measurement for AC current
Range
600.0 µA
6000 µA
60.00 mA
600.0 mA
10.00 A
All AC current ranges are specified from 5% to 100% of range
Frequency range: 45 Hz...400 Hz
DC current measurement
Range
600.0 µA
6000 µA
60.00 mA
600.0 mA
10.00 A
True RMS voltage measurement
Range
6.000 V
60.00 V
600.0 V
1000 V
All AC voltage ranges are specified from 5% to 100% of range
Input Impedance: 10 MΩ
Frequency range: 45 Hz...1000 Hz
66
11 Specifications
Resolution
0.1 µA
1 µA
0.01 mA
0.1 mA
0.01 A
Resolution
0.1 μA
1 μA
0.01 mA
0.1 mA
0.01 A
Resolution
0.001 V
0.01 V
0.1 V
1 V
CMM-30 – USER MANUAL
Accuracy
(1.0% m.v. + 3 digits)
(2.0% m.v. + 8 digits)
Accuracy
(1.0% m.v. + 3 digits)
(1.5% m.v. + 3 digits)
Accuracy
(1.0% m.v. + 5 digits)
(1.2% m.v. + 5 digits)