Code
VODIA Parameters
P107X
Engine oil pressure
Engine oil pressure, default value.
P107Z
Shutdown override
To disable the shut down override function, set the value to false.
P1PFL
Battery voltage 1, low limit
Set the alarm for battery voltage, low limit, between 18v - 32v.
P1PFM
Battery voltage 2, low limit
Set the alarm for battery voltage, low limit, between 18v - 32v.
P1PFN
Engine protection override request
To disable engine protection override while shutdown override is active , set
the value to 0.
Fig. 7
External yard connections
Label located on the inside of the door. Mark up any changes on label for future reference.
Outputs
X1 ............. SD override / harbour mode
X2 ............. Horn, internal use
X3 ............. Common alarm
X4 ............. Genset breaker(activated when load can be
applied: engine are running at rated speed)
X5 ............. Ready to start
X6 ............. Engine running
X7 ............. Ready to load engine
X8 ............. MCU power on
Combined Genset: Install 2x resistors on X1 and connect to SDM
1)
according to CAMS drawing.
Communication
34.............. Ground (preinstalled)
32-33 ........ MODBUS: RS 485A/B: External system or remote control.
30-31 ........ ComAps CAN (CAN 2), to remote panel, telematic sup-
port,
extension modules or Load sharing.
29.............. 8-pin Engine bus cable, pin 6
27-28 ........ BB2 CAN.
3
25-26 ........ For ComAps extension modules
Refer to ComAps Global guide for CAN bus termination.
2)
Pre-installed 120 Ohm resistor. Internal use only!
3)
Inputs
23-24 ........Speed request
11-22 .........Sets switch function
If customized, refer to ComAps Global guide for jumper settings.
4)
Refer to ComAps Global guide for CAN bus termination.
2)
Power
7-10 ..........0 V ground reference for switch
3-5 ............24 V (fused via SDM)
2................Constant power, engine connector A.
1................Remote panel power. Linked to POWER ON switch.
Value
True or False
True or False
18V - 32V
18V - 32V
0
1
2
(0-100%). Analog 4-20 mA (standard).
4
. Digital (standard).
2
loading